61
–
How to connect the connecting cable
1. Open the air inlet grille upward.
2. Remove the screws securing the front panel.
3. Slightly open the lower part of the front panel,
then pull the upper part of the front panel toward
you to remove it from the rear plate.
4. Insert the cond
u
it pipe (according to the local
codes
)
into the pipe hole on the wall.
5. Remove the conduit mount by loosening the fixing
screw. (Fig. 10-
4
-7)
6. Fix conduit pipe to conduit mount with
the
lock nut.
7. Pull out the connecting wire through the conduit pipe
and process the wire. (Fig. 10-
4
-
6
)
8. Take out the wire to the front and fix it to the terminal
block. Be careful not to mis-wir
e
(Fig. 10-
4
-
8
)
9. Firmly tighten the terminal screws to prevent them
from loosening. Tightening torque: 0.9 lbf. ft (1.2 N·m).
After tightening, pull the wires lightly to confirm that
they of not move.
10. Secure the connecting wire with the cord clamp.
11. Fix the conduit mount back to the body by fixing a screw.
12. Fix the front panel, terminal cover and air inlet grille
to
the indoor unit.
10-
4
-2. Wiring Connection
FILE NO. SVM-13069-3
Fig. 10-
4
-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the
unit falls.
•
In case the unit is to be installed in a block, brick, concrete or
similar type walls, make 3/16 in. (5 mm) dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
p
.
NOTE :
• Secure four corners and lower parts of the mounting
plate with 4 to 6 mounting screws to install it.
3/16 in. (5 mm) dia. hole
Clip anchor
(
field supplied parts
)
7
Mounting screw
Ø5/32 in. x 1 in.
(
∅
4 mm x 25 mm)
CAUTION
• Be sure to refer to the
system wiring diagram
located inside the front panel.
• Check local electrical
codes and also any
specific wiring instructions or limitations.
NOTE :
•
Use stranded wire only.
•
Wire type : minimum AWG14
CAUTION
L
1
L
2
S
L
1
L
2
S
Cord clamp
Terminal block
Terminal cover
Screw
Ground line
Screw
Connecting cable
Screw
Front panel
S
L
2
L
1
Ground
line
4-5/16 in. (110 mm)
3-5/32 in. (80 mm)
13/16 in. (20 mm)
3/8 in. (10 mm)
Conduit pipe
Conduit mount
Fixing screw
Lock nut
Interconnecting
cable