Toshiba RAS-05, RAS-07 Installation Manual Download Page 10

8

ELECTRICAL WORKS

ELECTRICAL WORKS

The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow 
the instruction as following.

Wiring Connection

     Indoor unit

     Outdoor unit

Valve cover

Terminals block

How to install the air inlet grille on the indoor 
unit

•  When attaching the air inlet grille, the contrary of the removed operation is 

performed. 

 

Wiring of the connecting cable can be carried out without removing the 
front panel.

1.  Remove the air inlet grille.
  Open the air inlet grille upward and pull it toward you.
2.  Remove the terminal cover and cord clamp.
3.  Insert the connecting cable (according to the local cords) into the pipe 

hole on the wall.

4.  Take out the connecting cable through the cable slot on the rear panel so 

that it protrudes about 20 cm from the front.

5.  Insert the connecting cable fully into the terminal block and secure it 

tightly with screws.

6.  Tightening torque : 1.2 N·m (0.12 kgf·m)
7.  Secure the connecting cable with the cord clamp.
8.  Fix the terminal cover and air inlet grille on the indoor unit.

Cord clamp

Terminal cover

Screw

Screws

Air inlet grille

Front panel

1.  Remove the valve cover, the electric parts cover and the cord clamp from 

the outdoor unit.

2.  Connect the connecting cable to the terminal as identi

fi

 ed by the 

matching numbers on the terminal block of indoor and outdoor unit.

3.  Insert the power cord and the connecting cable carefully into the terminal 

block and secure it tightly with screws.

4.  Use vinyl tape, etc. to insulate the cords which are not going to be used. 

Locate them so that they do not touch any electrical or metal parts.

5.  Secure the power cord and the connecting cable with the cord clamp.
6.  Attach the electric parts cover and the valve cover on the outdoor unit.

Model

RAS-05, 07BKV-E

RAS-10BKV-E

RAS-13BKV-E

RAS-16BKV-E

Power source

 50Hz, 220 – 240 V Single phase

Maximum running current

5.0A

6.7A

7.1A

8.0A

Circuit breaker rating

6.5A

8.5A

9.0A

10.0A

Power supply cable

H07RN-F or 60245 IEC66 (1.5 mm

2

 or more)

Connecting cable

Summary of Contents for RAS-05, RAS-07

Page 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1118350197 Indoor unit RAS 05 07 10 13 16BKV E Outdoor unit RAS 05 07 10 13 16BAV E ENGLISH ...

Page 2: ... 4 Indoor Unit Fixing 5 Drainage 5 OUTDOOR UNIT 6 Installation Place 6 Precautions about Installation in Regions with Snowfall and Cold Temperatures 6 Refrigerant Piping Connection 6 Evacuating 7 ELECTRICAL WORKS 8 Wiring Connection 8 Power Supply and Connecting Cable Connection 9 Power Supply Input Wiring Diagram 10 OTHERS 11 Gas Leak Test 11 Remote Control A B Selection 11 Test Operation 11 Auto...

Page 3: ...neighbors To avoid personal injury be careful when handling parts with sharp edges Please read this installation manual carefully before installing the unit It contains further important instructions for proper installation The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual Before installation please read these precautions for safe...

Page 4: ... screw 6 6 Flat head wood screw 2 7 Owner s Manual 1 8 Installation Manual 1 Outdoor Unit No Part name No Part name 9 Drain nipple 1 Cap water proof 2 Not require to use for RAS 05 07 10 13BAV E Air filters Clean every 2 weeks 1 Open the air inlet grille 2 Remove the air filters 3 Vacuum or wash and then dry them 4 Reinstall the air filters and close the air inlet grille ...

Page 5: ...it and wall and tilt the indoor unit for better operation For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat ...

Page 6: ...unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e ...

Page 7: ... piping After scribing slits of the back body with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After scribing slits of the back body with a knife or a making off pin cut them with a pair of nippers or an equivalent tool Slit Slit CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tightly In ...

Page 8: ...Drain the water from all the drain holes directly To protect the outdoor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 50 cm Install at least 50 cm ...

Page 9: ...dle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Using a vacuum pump CAUTION KEEP IMPORTANT 5 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the ai...

Page 10: ...tightly with screws 6 Tightening torque 1 2 N m 0 12 kgf m 7 Secure the connecting cable with the cord clamp 8 Fix the terminal cover and air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Connect the connecting cable to the terminal as identified by the...

Page 11: ...ect to 1 2 3 Terminal block L N 1 2 3 Earth line Power supply cable Connecting cable Earth line Connecting cable Stripping length of the connecting cable 3 50 mm Earth line 10 mm 70 mm 10 mm Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting cable connect to L 2 3 Terminal block L N 1 2 3 Earth line Connecting cable Connecting cable Stripping length of t...

Page 12: ...urn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Power supply input at Indoor unit Terminal Block Recommend Indoor Terminal...

Page 13: ...ating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B ro...

Page 14: ...ner has a history of the compressor failing and being replaced y When discolored oil a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the fo...

Page 15: ......

Page 16: ...1118350197 ...

Reviews: