 7)Ventilated area
    Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or 
    conducting any hot work. A degree of ventilation shall continue during the period that the work is carried 
    out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into 
    the atmosphere.

Repair and maintenance to electrical components shall include initial safety checks and component 
inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be 
connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately 
but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be 
reported to the owner of the equipment so all parties are advised.  
Initial safety checks shall include:  
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; 
That there no live electrical components and wiring are exposed while charging, recovering or purging 
the system; That there is continuity of earth bonding.

 8)Checks to the refrigeration equipment
    Where electrical components are being changed, they shall be fit for the purpose and to the correct 
    specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in 
    doubt consult the manufacturer's technical department for assistance. The following checks shall be 
    applied to installations using flammable refrigerants: 
    The charge size is in accordance with the room size within which the refrigerant containing parts are 
    installed; 
    The ventilation machinery and outlets are operating adequately and are not obstructed; 
    If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence 
    of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that 
    are illegible shall be corrected; 

Refrigeration pipe or components are installed in a position where they are unlikely to be exposed 

1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment 

9)Checks to electrical devices

7.Repairs to sealed components 

to any substance which may corrode refrigerant containing components, unless the components are 
constructed of materials which are inherently resistant to  being corroded or are suitably protected 
against being so corroded.

 The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure 
   the technician is aware of potentially flammable atmospheres. Ensure that the leak detection 
   equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately 
   sealed or intrinsically safe.
5)Presence of fire extinguisher
   If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate 
   fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher 
   adjacent to the charging area.
6)No ignition sources
   No person carrying out work in relation to a refrigeration system which involves exposing any pipe 
   work that contains or has contained flammable refrigerant shall use any sources of ignition in such a 
   manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette 
   smoking, should be kept sufficiently far away from the site of installation, repairing, removing and 
   disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior 
   to work taking place, the area around the equipment is to be surveyed to make sure that there are no 
   flammable hazards or ignition risks. No Smoking signs shall be displayed.

Summary of Contents for RACPD1212CRRC

Page 1: ...ITIONER Local Air Conditioner Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference ...

Page 2: ...recautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Choosing The Right Location Tools Needed Accessories Window Installation Kit Installation Troubleshooting Tips 03 11 11 12 12 12 12 13 13 14 16 18 19 20 22 22 22 22 23 ...

Page 3: ...s grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your unit must be used in a properly grounded wall receptacle If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker the fuse or circuit breake...

Page 4: ...hould be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Disconnect the power if strange sounds smell or smoke ...

Page 5: ... Wild disposal of waste in forests and landscapes endangers your health when hazar do us substances leak into the ground water and find their way into the food chain Do not use hazardous chemicals to clean or come into contact with the unit Do not use the unit in the presence of inflammable substances or vapour such as alcohol insecticides petrol etc Always transport your air conditioner in a vert...

Page 6: ...el shall be carried out under the supervision of the person competent in the use of flammable refrigerants AVERTISSEMENT Ne pas utiliser de produits permettant d accélérer le dégel ou de produits de nettoyage autres que ceux recommandés par le fabricant L appareil doit être entreposé dans un endroit sans source d allumage fonctionnant en continu par exemple flamme nue appareil au gaz en marche ou ...

Page 7: ...nside the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Work in confined spaces shall be avoided The area around the workspace shall be s...

Page 8: ...cuit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be corrected Refrigeration pipe or components are installed in a position where they are unlikely to be exposed 1 During repairs to sealed components all electrical supplies shall be disconnected from the ...

Page 9: ...he following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the re...

Page 10: ...b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment is available and being used correctly The recovery process is supervised at all times by a competent person Recovery equipment and cylinders conform to the appropriate standards d Pump down refrigeran...

Page 11: ...ly Installation Instructions Preparation NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly different The actual shape shall prevail The unit can be controlled by the unit control panel alone or with the remote controller This manual does not include Remote Controller Operations see the Remote Controller Instruction packed with the unit for detai...

Page 12: ... this could cause damage to the unit 50cm 19 7 inch 30cm 30cm 12inch 12inch 50cm 19 7inch Energy Rating Information The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts Diameter 150mm Length 1 5m Diameter 130mm Length 1 5m The Energy rating and noise information for unit with 3 meters extended exhaust duct is not assessed For some models NOTE We recommend that operating...

Page 13: ...aving the air feeling damp To find the proper air conditioner determine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amount of heat it can remove from a room A higher Why is the cooling capacity lower on newer models than on older units number means more co...

Page 14: ...ider A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 set 1 pc Window Slider B Remote Controller and Battery only for remote control models 1 pc Wall Exhaust Adaptor A only for wall installation models 2 ...

Page 15: ...the Adjustable Window Slider or or Window slider A MODEL A MODEL B Window slider B Bolt Window slider A Window slider B Bolt MODEL A MODEL B MODEL C MODEL D 1 2 Window slider A Window slider B Window slider C Bolts Window slider A Window slider B Window slider C Bolts Bolt Bolt Bolt 1 2 3 1 2 1 2 3 Bolt Bolt Bolt 1 2 3 4 Bolt Bolt Bolt 1 4 Bolt Window Sliders After assembly Before assembly Window ...

Page 16: ...em to the window sash and frame as shown 2 Insert the window slider assembly into the window opening Or Foam seal B Adhesive type shorter Foam seal A Adhesive type Foam seal B Adhesive type shorter Foam seal A Adhesive type Window slider A Window slider B if required Foam seal C Non adhesive type Or 2 Screws Security Bracket 3 Cut the non adhesive foam seal C strip to match the width or height of ...

Page 17: ...the wall for the Wall Exhaust Adaptor B 2 Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws provided in the kit 3 Connect the Exhaust Hose Assembly with Wall Exhaust Adaptor A to the Wall Exhaust Adaptor B NOTE Cover the hole using the adaptor cap when not in use max 120cm or 47 inch min 30cm or 12 inch Expansion anchor position Adaptor cap Wall Exhaust Adaptor B VENT...

Page 18: ...f WIRELESS light FOLLOW ME light Wireless light Used to initiate the Wireless function For the first time to use Wireless function press and hold the swing button for 3 seconds to initiate the Wireless connection mode The LED DISPLAY shows AP to indicate you can set Wireless connection If connection router is successful within 8 minutes the unit will exit Wireless connection mode automatically and...

Page 19: ...When the function is turned on the constant fan light will illuminate identifying the fan continuous run for cooling When the function is turned off the constant fan light will go out identifying the fan cycle run with compressor stop Sleep Eco button Used to initiate the SLEEP ECO operation Power button Power switch on off LED display Shows the set temperature in C or F F no display for some mode...

Page 20: ... Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remaining until start The system will automatically revert back to display the previous temperature setting if there is no operation in a 5 seconds period Turning the unit ON or OFF at any time or adju...

Page 21: ...out drain connector just attach the drain hose to the hole Place the open end of the Hose adaptor directly over the drain area in your basement floor that there are no kinks that will stop the warter flowing Place the end of the hose into the drain and make sure the end of the hose is down to let the water flow smoothly See Figs with Do never let it up See Figs with When the continuous drain hose ...

Page 22: ...unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and prevent mold Turn off the appliance and unplug it Clean the air filter according to the instructions in the previous section Reinstall the clean dry filter before storing Remove the batteries from the r...

Page 23: ... possible The unit is noisy and vibrates too much The unit makes a gurgling sound The ground is not level Place the unit on a flat level surface The air filter is blocked with dust or animal hair Turn off the unit and clean the filter according to instructions This sound is caused by the flow of refrigerant inside the unit This is normal Impedance Information To be in compliance EN 61000 3 11 the ...

Page 24: ...n and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version ...

Page 25: ......

Page 26: ...明书为单英文版本 不含型号及商标 也无制造商信息 请业务根据所 销售国家或者区域的法规要求 使用对应的官方语言版本 增加型号及其它 法规要求信息 重新申请订单编码说明书 3 基准说明书的显示标贴为PD全功能 包含了目前已有的所有图标和功能按键及其 操作说明 请业务和技术支持根据订单实际的显示标贴对说明书的显示标贴进行替换 对图标和功能及其说明进行相应删减 4 P22页ImpedanceInformation内容只适合部分由于电压波动和闪烁不合格要求增加阻抗声明 机型 其它无不合格要求的机型可以直接删除此内容 如保留制单要将美的市场型号 改为客户型号 5 后面的选配页面标明了对应的不同冷媒 可燃冷媒与非可燃冷媒 下要修改的内容 ...

Page 27: ...当机型为非可燃冷媒机型时 请进行以下变更 删除Pg6 Pg10 WARNING for Using R32 R290 Refrigerant 内容 ...

Reviews: