P9 ASD Installation and Operation Manual
Placing the P9 ASD in the
Hand
mode (Hand/Auto LED on) via the EOI places the
RS485
(2-wire)
control selection in the
Override Mode
for
Command
and
Frequency
input (see the section titled
for the proper setting). The
Hand/Auto
control
Override
feature for
Command
and
Frequency
(or either) may be enabled/disabled at Program
Utilities
Prohibition
Hand/
Auto Key
(Command or Frequency) Override.
Communications
may be used to place the remaining
Command
and eligible
Frequency
control input
sources in the
Override Mode
. Once placed in the
Override Mode
, this setting is valid until it is
cancelled, the power supply is turned off, or the P9 ASD is reset.
Override Operation
are scanned from left to right in the order that they are listed to determine
which input sources are in the
Override Mode
(active Command or Frequency command signal present).
The first item detected as having the
Override
function turned on is the selection that is used for
Command
or
Frequency
control input.
The
Override
control setting supersedes the setting of the
Command
mode setting (
) and the
Frequency
mode setting (
settings will be used in the event that the
register scan returns the condition that none of the listed items have the
Override
feature turned on or a
discrete input terminal is set to
Hand Priority
and is activated.
Command and Frequency-Control Override Hierarchy
lists the input conditions and the resulting output control source selections for
Command
and
Frequency
control
Override
operation.
The P9 ASD software reads the listed control sources from the left to the right as listed in
.
The first item to be read that has the
Override
feature turned on will be used for
Command
or
Frequency
control.
Table 4. Command and Frequency Control Hierarchy.
1
2
3
4
5
6
Priority Level
Forced F003/
F004 by I/P
Terminal
(Assign to Hand
Priority)
Comm.
Board
RS485
(4-Wire)
RS485
(2-Wire)
Terminal Board
(Binary/BCD Input)
F003/F004
Command/
Frequency Mode
1
X
X
X
X
X
F003/F004 Setting
0
1
X
X
X
X
Communication Board
0
0
1
X
X
X
RS485 (4-Wire)
0
0
0
1
X
X
RS485 (2-Wire)
0
0
0
0
1
X
Terminal Board
0
0
0
0
0
F003/F004
Setting
F003/F004 Setting
Note: 1
= Override feature is turned on for that control input source;
0
= Override Off;
X
= Don’t Care.