131
Figure 36. UP/Down Frequency Operation Control Timing Diagram.
Jump Frequency 1
Program
Special
Jump Frequencies
In conjunction with
, this parameter establishes a user-defined frequency
range: the
Jump Frequency
and a plus-or-minus value.
During acceleration, the output frequency of the ASD will hold at the lower
level of the
Jump Frequency
range until the programmed acceleration ramp
reaches the upper level of the
Jump Frequency
range, at which time the output
frequency of the ASD will accelerate to the upper level of the
Jump Frequency
range and continue upward as programmed.
During deceleration, the output frequency of the ASD will hold at the upper
level of the
Jump Frequency
range until the programmed deceleration ramp
reaches the lower level of the
Jump Frequency
range, at which time the output
frequency of the ASD will decelerate to the lower level of the
Jump
Frequency
range and continue downward as programmed.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects of
mechanical resonance.
Direct Access Number — F270
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz