5

Drain piping

 CAUTION

Following the Installation Manual, perform the 
drain piping work so that water is properly 
drained, and apply a heat insulation so as not to 
cause a dew dropping.
Inappropriate piping work may result in water 
leakage in the room and wet of furniture.

 

„

Piping / Heat insulating 
material

Require the following materials for piping and heat 
insulating at site.

Piping

Hard vinyl chloride pipe VP25 
(Outer dia. : Ø32 mm)

Heat insulator

Foam polyethylene :
Thickness 10 mm or more

 

„

Flexible hose

Use the attached 

fl

exible hose to adjust centre 

discrepancy of the hard vinyl chloride pipe or to adjust 
the angle.

 

y

Do not use the 

fl

exible hose as stretched, or do not 

deform it more extent than that in the following 

fi

gure.

 

y

Be sure to 

fi

x the soft end of the 

fl

exible hose with 

the attached hose band.

 

y

Use the 

fl

exible hose on a horizontal level.

OK

NO GOOD

max 

45°

Riser (Trap)

90° Bend

max 

45°

REQUIREMENT

 

y

Be sure to perform heat insulation of the drain 
pipes of the indoor unit.

 

y

Never forget to perform heat insulation of the 
connecting part with the indoor unit.

  An incomplete heat insulation causes dew 

dropping.

 

y

Set the drain pipe with downward slope (1/100 or 
more), and do not make swelling or trap on the 
piping.

  It may cause an abnormal sound.

Heat insulator

1/100 or more 

downward

Support 

bracket

1.5 m to 2 m

 

y

For length of the traversing drain pipe, restrict to 
20 m or less.

  In case of a long pipe, provide support brackets 

with interval of 1.5 to 2 m in order to prevent 
waving.

NO 

GOOD

Arched 

shape

Trap

 

y

Set the collective piping as shown in the below 

fi

gure.

As long as possible (10 cm)

VP25

VP25

VP25

VP30 or more

Downward slope 

1/100 or more

 

y

Be sure not to apply force to the connecting part of 
the drain pipe.

 

y

The hard vinyl-chloride pipe cannot be directly 
connected to the drain pipe connecting port of the 
indoor unit.

  For connection with the drain pipe connecting port, 

be sure to use / 

fi

x the attached 

fl

exible hose with 

the hose band, otherwise a damage or water leak 
is caused on the drain pipe connecting port.

Drain pipe 

connecting port 

(Hard socket)

Attached hose 

band

Attached 

fl

exible hose

VP25 vinyl chloride pipe 

(Locally procured)

Indoor unit

Soft socket

Hard socket

Socket for VP25 

(Locally procured)

Adhesive inhibited :

Use the attached 

fl

exible hose and hose band for 

connecting the drain hose to the clear drain socket.

If applying the adhesive, socket will be damaged and 

cause water leakage.

5 mm or less

10 to 12 mm

hose band tightening 

margin

VP25 vinyl chloride 

pipe

(Locally procured)

10 mm

Socket for VP25 vinyl 

chloride pipe

(Locally procured)

Flexible hose 

(Accessory)

Heat 

insulator

Drain pipe 

connecting port 

(Transparent)

Indoor unit

 

„

Connecting drain pipe

 

y

Connect a hard socket (locally procured) to the hard 
socket of the attached supplied 

fl

exible hose.

 

y

Connect a drain pipe (locally procured) to the 
connected hard socket.

REQUIREMENT

 

y

Connect hard vinyl chloride pipes securely using 
an adhesive for vinyl chloride to avoid water 
leakage.

 

y

It takes some time until the adhesive is dried and 
hardened (refer to the manual of the adhesive). 
Do not apply stress to the joint with the drain pipe 
during this time period.

 

„

Drain up

When a down-gradient cannot be secured for the drain 
pipe, drain-up piping is possible.

 

y

The height of the drain pipe must be 500 mm or less 
from the bottom of the ceiling.

 

y

Take the drain pipe out of the drain pipe joint with the 
indoor unit in 300 mm or less, and bend up the pipe 
vertically.

 

y

Immediately after the pipe is bent up vertically, lay 
the pipe making a down-gradient.

 

y

Set downward grading immediately after raising up 
vertically.

Indoor unit

Underside of ceiling

300 mm 

or less

Rising up 500 mm or less

Rising up  390 mm or less

 

„

Check the draining

In the test run, check that water drain is properly 
performed and water does not leak from the 
connecting part of the pipes.
Be sure to check draining also when installed in 
heating period.
Using a pitcher or hose, pour water (1500 to 2000 cc) 
into the suction port before installation of the ceiling 
panel.
Pour water gradually so that water does not spread on 
the motor of the drain pump.

 CAUTION

Pour water gently so that it does not spread around 
inside the indoor unit, which may cause a malfunction.

Heat exchanger

Drain pan

Float switch 

connector (3P)

(CN34: red)

Tool for 

pouring water

Bottle

Water (1500 cc to 2000 cc)

Insert the hose end 

between the heat 

exchanger and 

the drain pan, and 

then bend the hose 

downward.

Power 

supply 

wiring

 

y

After the electric work has 

fi

nished, pour water 

during COOL mode operation.

 

y

If the electric work has not yet 

fi

nished, pull out 

the 

fl

oat switch connector (CN34: Red) from the 

electrical control box, and check draining by plugging 
the single phase 208-240V power to the terminal 
blocks R(L) and S(N).

  If doing so, the drain pump motor operates.
  (Never apply 208-240V to 

U

1

U

2

A

 or 

B

, otherwise 

a trouble of P.C. board occurs.)

Summary of Contents for MMU-UP0031YHP-E

Page 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name 1 way Cassette type MMU UP0031YHP E MMU UP0051YHP E MMU UP0071YHP E MMU UP0091YHP E MMU UP0121YHP E For commercial use English ...

Page 2: ... oder weniger gemäss EN ISO 7779 Information If U series models TU2C Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Content...

Page 3: ...individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carri...

Page 4: ...the installation maintenance repair or removal work set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Warning indications on the air conditioner unit W...

Page 5: ...product is broken contact the dealer When the air conditioner must be transported by hand carry it by two or more people Do not move or repair any unit by yourself There is high voltage inside the unit You may get electric shock when removing the cover and main unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Sele...

Page 6: ...hich is designed to be used outdoors Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is n...

Page 7: ...he non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the inst...

Page 8: ... The installation fuse all types can be used must be used for the power supply line of this conditioner 1 Refer to the Definition of Qualified Installer or Qualified Service Person 2 Accessory parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R ...

Page 9: ...bour pay due attention to the level of noise y Place with poor ventilation Before air ducting work check whether value of air volume static pressure and duct resistance are correct y Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials...

Page 10: ... a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Using the installation pattern accessory The installation patt...

Page 11: ...y Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage y Remove the adjust corner caps at the four corners of the ceiling panel and then install the ceiling panel onto the indoor unit y Make sure that the claws of the four adjust corner caps are securely fit Im...

Page 12: ... the clear drain socket If applying the adhesive socket will be damaged and cause water leakage 5 mm or less 10 to 12 mm hose band tightening margin VP25 vinyl chloride pipe Locally procured 10 mm Socket for VP25 vinyl chloride pipe Locally procured Flexible hose Accessory Heat insulator Drain pipe connecting port Transparent Indoor unit Connecting drain pipe y Connect a hard socket locally procur...

Page 13: ... indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Pipe size mm Gas side Liquid side Ø9 5 Ø6 4 Connecting refrigerant piping Flaring 1 Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare n...

Page 14: ...iling side Wrap the pipe with the attached heat insulator without any gap between the indoor unit Flare nut Heat insulator of the pipe Banding band Locally procured Union Heat insulation pipe Accessory 7 Electrical connection WARNING y Use the specified wires for wiring connection to the terminals Securely fix them to prevent external forces applied to the terminals from affecting the terminals In...

Page 15: ...nd model names Communication type TU2C Link U series and future models TCC Link Other than U series Outdoor unit MMY MUPÛÛÛ This letter indicates U series model Other than U series MMY MHPÛÛÛ MMY MAPÛÛÛ MCY MHPÛÛÛ Indoor unit MMÛ UPÛÛÛ This letter indicates U series model Other than U series MMÛ APÛÛÛ Wired remote controller RBC ASCUÛÛÛ This letter indicates U series model Other than U series Wire...

Page 16: ...connection causes a trouble y Be sure to pass the wires through the bushing of wiring connection port of the indoor unit y Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing etc y The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit y Make a loop on the wire for margin of the length so that the electrical cont...

Page 17: ...utdoor Outdoor unit Follower outdoor Earth terminal Earth terminal S The ground of a shielded wire S The ground of a shielded wire Control wiring between outdoor units Shield wire Control wiring between indoor and outdoor units Shield wire Control wiring between indoor units Shield wire Indoor unit Earth Earth Earth Earth Indoor unit Indoor unit Indoor unit Remote controller Indoor power supply 22...

Page 18: ... Change the setup while the air conditioner is not working CAUTION Set only the Code No shown in the following table Do NOT set any other Code No If a Code No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push and hold menu button and setting button simultaneously for 10 seconds or more y After a while the display flashes as ...

Page 19: ...E No in Procedure 3 y Select the following data for the SET DATA in Procedure 4 SET DATA 0000 0001 Remote controller sensor Not used factory default Used When flashes the remote controller sensor is defective Select the SET DATA 0000 not used or replace the remote controller 9 Test run Before test run y Before turning on the circuit breaker carry out the following procedure 1 By using insulation t...

Page 20: ...ng heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by the remote controller 2 Open the air intake grille y Slide the button of the air intake grille inward and open the air intake grille slowly while holding it Hook lock grille Hook lock grille Grille air intake Screw Direction to open Direction to open Push hook Cleaning of air filters If the air fi...

Page 21: ...alance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louver...

Page 22: ...outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote control...

Page 23: ... ALT Ps sensor trouble I F F24 F24 ALT Pd sensor trouble I F F29 SIM Indoor unit other trouble Indoor unit F30 F30 SIM Occupancy sensor trouble Indoor unit F31 F31 SIM Indoor unit EEPROM trouble I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down Inverter H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock Inverter H03 H03 01 Comp 1 side 02 Comp ...

Page 24: ... trouble I F P01 ALT Indoor fan motor trouble Indoor unit P03 P03 ALT Discharge temp TD1 trouble I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation Inverter P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage troub...

Page 25: ...3 08 Fan 1 05 Comp 1 Comp 3 09 Comp 1 Fan 1 06 Comp 2 Comp 3 0A Comp 2 Fan 1 07 Comp 1 Comp 2 Comp 3 0B Comp 1 Comp 2 Fan 1 08 Fan 10 Fan 2 09 Comp 1 Fan 11 Comp 1 Fan 2 0A Comp 2 Fan 12 Comp 2 Fan 2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan 2 0C Comp 3 Fan 18 Fan 1 Fan 2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan 1 Fan 2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan 1 Fan 2 0F All 1B All Inverter trouble Inverter t...

Page 26: ... E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law NOTE This declaration becomes invalid if technical or operational modifications are introduced wi...

Page 27: ...door unit installed room m Concentration limit kg m The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg Outdoor unit e g charged amount 15 kg Indoor unit Room A Room B Room C Room D ...

Page 28: ...o 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 High ceiling setup CODE No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE N...

Page 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1127650301 ...

Reviews: