background image

8-EN

7-EN

– 4 –

• Only a quali

fi

ed installer(*1) or quali

fi

ed service person(*1) is 

allowed to undertake work at heights using a stand of 50 cm 
or more or to remove the intake grille of the indoor unit to 
undertake work.

• Wear protective gloves and safety work clothing during 

installation, servicing and removal.

• Do not touch the aluminium 

fi

n of the unit. You may injure 

yourself if you do so. If the 

fi

n must be touched for some 

reason, 

fi

rst put on protective gloves and safety work clothing, 

and then proceed.

• Do not climb onto or place objects on top of the outdoor unit. 

You may fall or the objects may fall off of the outdoor unit and 
result in injury.

• When work is performed at heights, use a ladder which 

complies with the ISO 14122 standard, and follow the 
procedure in the ladder’s instructions. Also wear a helmet for 
use in industry as protective gear to undertake the work.

• Before cleaning the 

fi

lter or other parts of the outdoor unit, set 

the circuit breaker to OFF without fail, and place a “Work in 
progress” sign near the circuit breaker before proceeding with 
the work.

• Before working at heights, put a sign in place so that no-one will 

approach the work location, before proceeding with the work. 
Parts and other objects may fall from above, possibly injuring 
a person below. While carrying out the work, wear a helmet for 
protection from falling objects.

• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. 

If any part of the product is broken, contact the dealer.

• When the air conditioner must be transported by hand, carry it 

by two or more people.

• Do not move or repair any unit by yourself. There is high voltage 

inside the unit. You may get electric shock when removing the 
cover and main unit.

• This appliance is intended to be used by expert or trained users 

in shops, in light industry, or for commercial use by lay persons.

Selection of installation location

• When the air conditioner is installed in a small room, provide 

appropriate measures to ensure that the concentration of 
refrigerant leakage occur in the room does not exceed the 
critical level.

• Do not install in a location where 

fl

ammable gas leaks are 

possible. If the gas leak and accumulate around the unit, it may 
ignite and cause a 

fi

re.

• To transport the air conditioner, wear shoes with additional 

protective toe caps.

• To transport the air conditioner, do not take hold of the bands 

around the packing carton. You may injure yourself if the bands 
should break.

• Install the indoor unit at least 2.5 m above the 

fl

oor level since 

otherwise the users may injure themselves or receive electric 
shocks if they poke their 

fi

ngers or other objects into the indoor 

unit while the air conditioner is running.

• Do not place any combustion appliance in a place where it is 

directly exposed to the wind of air conditioner, otherwise it may 
cause imperfect combustion.

Installation

• When the indoor unit is to be suspended, the designated 

hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be 
used.

• Install the air conditioner securely in a location where the base 

can sustain the weight adequately. If the strength is not enough, 
the unit may fall down resulting in injury.

Summary of Contents for MMU-UP0031YHP-E

Page 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name 1 way Cassette type MMU UP0031YHP E MMU UP0051YHP E MMU UP0071YHP E MMU UP0091YHP E MMU UP0121YHP E For commercial use English ...

Page 2: ... oder weniger gemäss EN ISO 7779 Information If U series models TU2C Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Content...

Page 3: ...individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carri...

Page 4: ...the installation maintenance repair or removal work set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Warning indications on the air conditioner unit W...

Page 5: ...product is broken contact the dealer When the air conditioner must be transported by hand carry it by two or more people Do not move or repair any unit by yourself There is high voltage inside the unit You may get electric shock when removing the cover and main unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Sele...

Page 6: ...hich is designed to be used outdoors Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is n...

Page 7: ...he non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the inst...

Page 8: ... The installation fuse all types can be used must be used for the power supply line of this conditioner 1 Refer to the Definition of Qualified Installer or Qualified Service Person 2 Accessory parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R ...

Page 9: ...bour pay due attention to the level of noise y Place with poor ventilation Before air ducting work check whether value of air volume static pressure and duct resistance are correct y Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials...

Page 10: ... a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Using the installation pattern accessory The installation patt...

Page 11: ...y Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage y Remove the adjust corner caps at the four corners of the ceiling panel and then install the ceiling panel onto the indoor unit y Make sure that the claws of the four adjust corner caps are securely fit Im...

Page 12: ... the clear drain socket If applying the adhesive socket will be damaged and cause water leakage 5 mm or less 10 to 12 mm hose band tightening margin VP25 vinyl chloride pipe Locally procured 10 mm Socket for VP25 vinyl chloride pipe Locally procured Flexible hose Accessory Heat insulator Drain pipe connecting port Transparent Indoor unit Connecting drain pipe y Connect a hard socket locally procur...

Page 13: ... indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Pipe size mm Gas side Liquid side Ø9 5 Ø6 4 Connecting refrigerant piping Flaring 1 Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare n...

Page 14: ...iling side Wrap the pipe with the attached heat insulator without any gap between the indoor unit Flare nut Heat insulator of the pipe Banding band Locally procured Union Heat insulation pipe Accessory 7 Electrical connection WARNING y Use the specified wires for wiring connection to the terminals Securely fix them to prevent external forces applied to the terminals from affecting the terminals In...

Page 15: ...nd model names Communication type TU2C Link U series and future models TCC Link Other than U series Outdoor unit MMY MUPÛÛÛ This letter indicates U series model Other than U series MMY MHPÛÛÛ MMY MAPÛÛÛ MCY MHPÛÛÛ Indoor unit MMÛ UPÛÛÛ This letter indicates U series model Other than U series MMÛ APÛÛÛ Wired remote controller RBC ASCUÛÛÛ This letter indicates U series model Other than U series Wire...

Page 16: ...connection causes a trouble y Be sure to pass the wires through the bushing of wiring connection port of the indoor unit y Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing etc y The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit y Make a loop on the wire for margin of the length so that the electrical cont...

Page 17: ...utdoor Outdoor unit Follower outdoor Earth terminal Earth terminal S The ground of a shielded wire S The ground of a shielded wire Control wiring between outdoor units Shield wire Control wiring between indoor and outdoor units Shield wire Control wiring between indoor units Shield wire Indoor unit Earth Earth Earth Earth Indoor unit Indoor unit Indoor unit Remote controller Indoor power supply 22...

Page 18: ... Change the setup while the air conditioner is not working CAUTION Set only the Code No shown in the following table Do NOT set any other Code No If a Code No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push and hold menu button and setting button simultaneously for 10 seconds or more y After a while the display flashes as ...

Page 19: ...E No in Procedure 3 y Select the following data for the SET DATA in Procedure 4 SET DATA 0000 0001 Remote controller sensor Not used factory default Used When flashes the remote controller sensor is defective Select the SET DATA 0000 not used or replace the remote controller 9 Test run Before test run y Before turning on the circuit breaker carry out the following procedure 1 By using insulation t...

Page 20: ...ng heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by the remote controller 2 Open the air intake grille y Slide the button of the air intake grille inward and open the air intake grille slowly while holding it Hook lock grille Hook lock grille Grille air intake Screw Direction to open Direction to open Push hook Cleaning of air filters If the air fi...

Page 21: ...alance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louver...

Page 22: ...outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote control...

Page 23: ... ALT Ps sensor trouble I F F24 F24 ALT Pd sensor trouble I F F29 SIM Indoor unit other trouble Indoor unit F30 F30 SIM Occupancy sensor trouble Indoor unit F31 F31 SIM Indoor unit EEPROM trouble I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down Inverter H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock Inverter H03 H03 01 Comp 1 side 02 Comp ...

Page 24: ... trouble I F P01 ALT Indoor fan motor trouble Indoor unit P03 P03 ALT Discharge temp TD1 trouble I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation Inverter P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage troub...

Page 25: ...3 08 Fan 1 05 Comp 1 Comp 3 09 Comp 1 Fan 1 06 Comp 2 Comp 3 0A Comp 2 Fan 1 07 Comp 1 Comp 2 Comp 3 0B Comp 1 Comp 2 Fan 1 08 Fan 10 Fan 2 09 Comp 1 Fan 11 Comp 1 Fan 2 0A Comp 2 Fan 12 Comp 2 Fan 2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan 2 0C Comp 3 Fan 18 Fan 1 Fan 2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan 1 Fan 2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan 1 Fan 2 0F All 1B All Inverter trouble Inverter t...

Page 26: ... E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law NOTE This declaration becomes invalid if technical or operational modifications are introduced wi...

Page 27: ...door unit installed room m Concentration limit kg m The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg Outdoor unit e g charged amount 15 kg Indoor unit Room A Room B Room C Room D ...

Page 28: ...o 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 High ceiling setup CODE No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE N...

Page 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1127650301 ...

Reviews: