PROGRAMMING
TMS7 SERIES
ME00070B
25
CAUTION
NOTE:
Function 20.
Local/Remote Operation
can be used
to limit operation to either local or remote mode
operation. If the
<LOCAL/REMOTE>
push button is
used in an attempt to switch to a prohibited mode
the numeric display will show 'OFF'.
CAUTION
NOTE:
Simultaneously pressing the
<STOP>
and
<RESET>
push buttons causes the TMS7 to
immediately remove voltage from the motor,
resulting in a coast to stop. Any soft settings are
ignored.
4.
Programming Buttons:
Refer to section 7.1.
5.
Remote Control Inputs Status:
These LEDs indicate the
state of the circuits across the TMS7 remote control inputs.
CAUTION
NOTE:
All LEDs and the Numeric display are illuminated
for approx imately 1 second to test their operation
when control power is first applied .
Remote control.
TMS7 operation can be controlled via the remote control inputs
when the soft starter is in remote mode. Use the
<LOCAL/REMOTE>
push button to switch between local and
remote modes. Refer to section 6.3
Control Wiring
for further
detail.
Restart delay.
Function 31.
Restart Delay
sets the delay period between the
end of a stop and the beginning of the next start. During the
restart delay period the LEDs to the right of the numeric display
will flash indicating that a restart cannot yet be attempted.
Pre-start tests.
Before applying voltage to the motor when a start is initiated, the
TMS7 first performs a series of tests to check the motor
connection and supply conditions.
Secondary motor settings.
TMS7 starters can be programmed with two motor parameter
sets. The primary motor parameters are set using functions 1~9.
The secondary motor parameters are set using functions 80~88.
When commanded to start the TMS7 checks the state of the
FLC Select input (Terminals I43 & I44). In the event of an open
circuit the primary motor settings are used. In the event of a
closed circuit the secondary motor settings are used.
FLC Select
I43
I44
Primary Motor Settings
Function Settings 1 ~ 9
I43
I44
Primary Motor Settings
Function Settings 80 ~ 88
FLC Select