6. Fault Code and Display Information
Multi Controller Display Switch Information
ThX
15
ThD
14
ThC
13
ThB
12
Displays Sensor Readings As A Hexadecimal Code :
40=0ºC ; 68=10ºC ; 90=20ºC ; b8=30ºC
ThA
11
PMVD
10
PMVC
9
PMVB
8
Displays Degree Of PMV Opening As A Hexadecimal Code :
(OO) = Closed , (FO) = Fully Open
PMVA
7
Indicates Faulty Branch Connection After Circuit Test
Displays Branch Being Tested (A b C d)
cct test
6
Normal Display (OO), Restart Timer Displays (-1) During Count Down
Timer
5
Operating Mode :Heating (H-), Cooling (-C), Stop (--), Defrost (J-)
4
Displays “dF” during defrost operation
Defrost
Oil Ret
brchC
Superheat
brchC
Superheat
brchD
Oil Ret
brch D
Oil Ret
brchA
Superheat
brchA
Superheat
brchB
Oil Ret
brch B
3
Level of Cooling/Heating Demand (00-1F)
Demand
2
For Details of Fault Codes see Page 13
Fault
Codes
1
To
Outdoor
From C
Branch
To C
Branch
To D
Branch
From D
Branch
From
Outdoor
From A
Branch
To A
Branch
To B
Branch
From B
Branch
Serial
0
_
|
_
_
|
|_|
_
|
|
_|
|_|
_
|_|
|
|
_|
_
|_|
|
_
_
|
_
|_|
|_
|
|
_
|_
|
|
|_|
_
_
|_|
|_|
_
|
_
_
|
|_|
_
|
|
_|
|_|
_
|_|
|
|
_|
_
|_|
|
_
_
|
_
|_|
|_
|
|
_
|_
|
|
|_|
_
_
|_|
|_|
LD 2
LD 1
Indicates
Switch
Pos.
The Hexadecimal codes can be interpreted using the following chart
90
1F
41
OF
240
FO
87.5
1
37.9
OE
224
EO
84.4
1D
34.8
Od
208
dO
81.3
1C
31.7
OC
32
192
CO
78.2
1B
28.6
Ob
28
176
bO
75.1
1A
25.5
OA
24
160
AO
72
19
22.4
O9
20
144
9O
68.9
18
19.3
O8
16
128
8O
65.8
17
16.2
O7
12
112
7O
62.7
16
13
O6
8
96
6O
59.6
15
10
O5
4
80
5O
56.5
14
6.9
O4
0
64
4O
53.4
13
3.9
O3
-4
48
3O
50.3
12
0
O2
-8
32
2O
47.2
11
0
O1
16
1O
44.1
1O
0
OO
Closed
OO
Hz
Display
Hz
Display
ºC
Angle
Level Of Demand
Th-AbCdX
PMV-
Display
The above chart shows a sample of readings, other intermediate readings may be registered.