[P15]
Cause
Check code
Check code name
Gas leak detection
TS condition (Sub-code: 01)
1.
Outdoor unit service valve closed
2. Outdoor
PMV
error
3. TS1
sensor
error
4.
Refrigerant shortage, clogging refrigerant circuit
5.
4-way valve error
6.
SV4 circuit error
Are service valves
at gas and liquid
side fully opened?
Open service valves fully
.
Repair outdoor PMV
.
Replace TS1
sensor
.
Check and replace 4-way
valve and coil.
Repair
SV41/SV42 valve
circuits.
Refrigerant shortage,
clogging, pipe breakage.
(Check there is no clogging and pipe
breakage, and then recharge refrigerant.)
(Coil, valve body
, disconnection
of wire, etc.)
Are
characteristics
of TS1
sensor
resistance
normal?
Does discharge
refrigerant gas bypass
to suction side through
4-way valve?
Is there any
leakage on SV41
and
SV
4
2
valve
circuits?
No
Connectors: PMV1: CN300,
PMV
3
: CN30
2
, PMV4: CN303
Is outdoor PMV normal?
1. Connector connection
Wiring
2.
Coil
3.
4. V
alve body
5. Outdoor I/F P
.C. board
Ye
s
Ye
s
No
No
No
Ye
s
No
Ye
s
No
Ye
s
Ye
s
No
Ye
s
No
Ye
s
Ye
s
[P13]
Check code
Check code name
Outdoor liquid back detection
error
Cause
1.
PMV1/PMV3/PMV4
error
2.
Pd sensor
, Ps sensor error
3.
Clogging of SV2 circuit
4.
Clogging of SV3B circuit and/or balance pipe
5.
Leakage at a check valve on a main discharge pipe
6.
Outdoor I/F P
.C. board error
Are
connections of outdoor
PMV1/PMV
3
/PMV4
connectors correct?
Are
operations of outdoor
PMV1/PMV
3
/PMV4
normal?
Are
characteristics of
Pd sensor/Ps sensor
output voltage
normal?
Is SV2 valve coil
correctly connected?
Are balance pipe
service valves of
all units fully
opened?
Is there no
clogging of SV3B
valve?
Is there no
clogging of SV3B valve
of any other unit than
malfunctioning one?
Correct connector connection.
(PMV1: CN300, PMV
3
:
CN30
2
, PMV4: CN303)
PMV error
Pd sensor/Ps sensor error
Correct connector connection.
(
S
V2: CN3
11
)
Open fully balance pipe
service valves of all units.
Replace clogging parts.
Replace clogging parts.
Replace check valve of main
discharge pipe.
Check I/F P
.C. board.
Is there no leakage of
check valve of main
discharge pipe in follower
units in which compressors
are driven in cooling
operation?
* Se
e “Ou
tdo
or
un
it
te
mp
erat
ur
e s
enso
r
characteristics” on
“8-
10
.
Sensor Charac
teristics”.
−
211
−
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MAP1406HT8(J)P
Page 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...