INSTALLATION OF OUTDOOR UNIT
WARNING
Perform a specified installation work against a strong wind such as typhoon or earthquake.
If the air conditioner is imperfectly installed, an accident by falling or dropping may be caused.
Install the air conditioner certainly at a place bearable to weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Drain water is discharged from the outdoor unit. (Especially in heating time)
Install the outdoor unit at a place where has good drainage.
For installation, be careful to the strength and the level of the foundation so that an abnormal
sound (Vibration, noise) does not generate.
In the snowfall area, apply the following measures against
snowfall for the outdoor unit. (See the figure on the right.)
(Incomplete snowfall-proof measures causes a trouble.)
Place a higher stool under the unit, and mount the
snowfall-hoods to air inlet and air outlet so that
snows do not have influence.
(For the above works, please arrange at the field.)
1. To install the multiple outdoor units, arrange them with
20mm or more intervals.
Fix each outdoor unit with M12 anchor bolts at 4 positions.
Length by 20mm is appropriate for an anchor bolt.
• Anchor bolt pitch is as shown below:
2. When drawing out the refrigerant pipe from underside, set
height of the stool by 500mm or more.
20mm or more
20mm or more
M12 anchor bolt
4 positions/unit
20
700
310 or more
*
310 or more
700
700
755
Continuous hole
(15 x 20 long hole)
500mm or more
Snowfall-hood
for air outlet
Snowfall-hood
for air inlet
(4 faces)
Stool
Space for draining