13
REQUIREMENT
• When a group control is performed over the
multiple refrigerant lines, be sure to turn on the
power supplies of all the indoor units connected in
a group in the time of address setup.
• If turning on the power for each refrigerant line to
set up address, a header indoor unit is set for
each line. Therefore, an alarm code “L03”
(Duplicated indoor header units) is output in
operation after address setup. In this case,
change the group address from the wired remote
controller so that only one header unit is set up.
(Example)
Wire
systematic
diagram
Group control over
multiple refrigerant lines
Address setup procedure 2
Using SW13 and 14 on the interface P.C. board of the header
unit in each system, set up the system address for each system.
(At shipment from factory: Set to Address 1)
Note) Be careful not to duplicate with other refrigerant line or other
system address.
System address switch on outdoor interface P.C. board
(
¡
: Switch ON,
×
: Switch OFF)
: Is not used for setup of system address. (Do not change setup.)
Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all the header units to
which the central control is connected. (At shipment from factory: No connection of connector)
SW11
1
ON
Header unit interface P.C. board
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON
ON
ON
ON
2 3 4
SW09
SW08
1
1
2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
Turn on power of indoor/outdoor.
(In order of indoor
→
→
→
→
→
outdoor)
After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the
header unit.
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1
→
→
→
→
→
Auto 2
→
→
→
→
→
Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup
finished.
Procedure
to
are repeated in other refrigerant lines.
Outdoor
Header
Indoor
Indoor
Remote
controller
Outdoor
Indoor
Indoor
2
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
For internal
wiring between
outdoor units
7
ADDRESS SETUP
System
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SW13
SW14
1
2
3
4
1
2
3
4
×
×
×
×
×
×
¡
×
×
×
×
×
¡
×
×
×
¡
¡
×
×
×
×
×
¡
×
×
¡
×
¡
×
×
×
¡
¡
×
×
¡
¡
¡
×
×
×
×
×
¡
×
¡
×
×
¡
×
×
¡
×
¡
×
¡
¡
×
¡
×
×
×
¡
¡
×
¡
×
¡
¡
System
address
15
16
17
18
19
20
21
22
23
24
25
26
27
28
SW13
SW14
1
2
3
4
1
2
3
4
×
×
¡
¡
¡
×
¡
¡
¡
¡
¡
×
×
×
×
¡
¡
×
×
×
¡
×
¡
×
×
¡
¡
¡
×
×
¡
×
×
¡
×
¡
¡
×
¡
×
¡
×
¡
¡
×
¡
¡
¡
¡
×
¡
×
×
×
¡
¡
¡
×
×
¡
¡
×
¡
×
¡
¡
¡
¡
×
¡