24
−
6 F 8 A 0 9 3 4
4.4 Grounding
CAUTION
Do not wire cables and replace parts
when power is supplied.
Do not work on piping and wiring
with wet hands
.
DON’T
Wiring work and replacing
parts in the power-on state
may cause electric shock.
DON’T
Wet hands may result in
electric shock
.
Ground as shown in Figure 4.10. Make the grounding wire as short as possible.
Use
grounding wire material of IV wire 5.5mm
2
or more. Do not share a grounding wire
with other instruments where grounding current may flow. (An independent
grounding is preferable.)
Figure 4.10 Grounding the LF516/LF546 Type
Grounding terminal
grounding resistance
100
Ω
or more
•
If the piping material is
conductive
, connect
the grounding wires to the both ends of the
piping flange.
•
If the piping material is
non-conductive
, perform
grounding (grounding resistance
100Ω
or less).
Conductive material pipe
Example: Metal, etc.
Piping of non-conductive material
Example: Resin or metal piping whose
inside is resin-lined, etc.
Grounding wire