– 41 –
Hydro Unit
Installation Manual
A04
Antifreeze operation
O
×
1. Almost no or little water flow.
• Dirt clogging in the water piping system.
• The water piping is too long or too short.
2. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
3. Set the presence of the backup heater.
4. Check the water inlet, water outlet and heat exchange
(TWI, TWO, TC) sensors and Flow Switch.
A05
Piping antifreeze operation
O
O
1. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
2. Check the water inlet, water outlet and heater outlet
sensors (TWI, TWO, THO).
3. Disconnection of the backup heater.
A08
Low pressure sensor operation
error
O
×
1. Almost no or little water flow.
2. Defect of the flow switch.
3. On-load cooling or prolonged defrosting (a lot of frost
formation) under the above conditions.
4. Defect in the low pressure sensor.
5. Check the refrigeration cycle (gas leak).
A09
Overheat protection operation
(Thermostat of the backup heater)
O
×
1. No water (heating without water) or no water flow.
2. Defect of the flow switch.
3. Defect of the backup heater (poor automatic reset
thermostat).
A10
Antifreeze operation 2
×
×
1. Almost no or little water flow.
2. Check the water inlet, water outlet and heat exchange
(TWO, TC) sensors.
A11
Operation of the release protection
Heating
Cooling
×
Hot water
O
×
1. Almost no water flow.
2. Defect of the flow switch.
3. Check the water outlet temperature sensor (TWO).
A12
Heating, hot water heater error
O
O
1. Activated by a large load of heating or hot water
supply.
2. Check the heater power circuit (backup or hot water
cylinder heater).
• Power supply voltage, breaker, power supply
connection
E03
Regular communication error
between hydro unit and remote
controller
×
O
1. Check remote controller connection.
2. Defect in the remote controller.
E04
Regular communication error
between hydro unit and outdoor
unit
O
O
1. Check the serial circuit.
• Miswiring of the crossover between the hydro unit and
the outdoor unit
F03
TC sensor error
O
O
1. Check the resistance value and connection of the
heat exchange temperature sensor (TC).
F10
TWI sensor error
O
O
1. Check the resistance value and connection of the
water inlet temperature sensor (TWI).
F11
TWO sensor error
×
O
1. Check the resistance value and connection of the
water outlet temperature sensor (TWO).
O ... Possible
× .... Not possible
Check
code
Diagnostic functional operation
Determination and action
Operational cause
Backup
present
Automatic
reset
41-EN