142
GX9 ASD Installation and Operation Manual
Commercial Power/ASD Switching Frequency
Program
Terminal
Line Power Switching
When enabled at
and with a properly configured discrete output terminal,
this parameter sets the frequency at which the
At Frequency Powerline
Switching
function engages.
The
At Frequency Powerline Switching
function commands the system to
discontinue using the output of the ASD and to switch to commercial power
once reaching the frequency set here.
See parameter
for more information on this setting.
Direct Access Number — F355
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
ASD-Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will wait before
outputting a signal to the motor once the switch-to-ASD-output criteria has
been met.
See parameter
for more information on this setting.
Direct Access Number — F356
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — (ASD-Dependent)
Maximum — 10.00
Units — Seconds
Commercial-Power-Side Switching Waiting Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
See parameter
for more information on this setting.
Direct Access Number — F357
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum —
(ASD-Dependent)
Maximum — 10.00
Units — Seconds
Commercial Power Switching Freq. Hold Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-ASD-output criteria has
been met.
See parameter
for more information on this setting.
Direct Access Number — F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
PID Feedback Signal Selection
Program
Feedback
Feedback Settings
This parameter
Enables/Disables
PID
feedback control. When enabled, this
parameter determines the source of the motor control feedback.
Settings:
0 — PID Control Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
Proportional-Integral-Derivative
(PID) — A closed-loop control technique
that seeks error minimization by reacting to three values: One that is
proportional to the error, one that is representative of the error, and one that is
representative of the rate of change of the error.
Direct Access Number — F360
Parameter Type —
Selection List
Factory Default —
PID Control
Disabled
Changeable During Run —
Yes
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......