GX9 ASD Installation and Operation Manual
V/f Five-Point 3 Frequency
Program
Special
V/f 5-Point Setting
The
V/f Five-Point 3 Frequency
sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point 3 Voltage).
See
for additional information on this setting.
Direct Access Number — F194
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
No
Minimum — 0
Maximum —
Max. Freq.
Units — Hz
V/f Five-Point 3 Voltage
Program
Special
V/f 5-Point Setting
The
V/f 5-Point 3 Voltage
establishes the output voltage level that is to be
associated with the frequency setting of
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
Se
e
for additional information on this setting.
Direct Access Number — F195
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — V or % (
)
Units — V or % (
)
V/f Five-Point 4 Frequency
Program
Special
V/f 5-Point Setting
The
V/f Five-Point 4 Frequency
sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point 4 Voltage).
See
for additional information on this setting.
Direct Access Number
— F196
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
No
Minimum — 0
Maximum —
Max. Freq.
Units — Hz
V/f Five-Point 4 Voltage
Program
Special
V/f 5-Point Setting
The
V/f 5-Point 4 Voltage
establishes the output voltage level that is to be
associated with the frequency
setting of
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is
%
.
See
for additional information on this setting.
Direct Access Number — F197
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — V or % (
)
Units — V or % (
)
V/f Five-Point 5 Frequency
Program
Special
V/f 5-Point Setting
The
V/f Five-Point 5 Frequency
sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point 5 Voltage).
See
for additional information on this setting.
Direct Access Number — F198
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
No
Minimum — 0
Maximum —
Max. Freq.
Units — Hz
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......