V/f Five-Point 5 Voltage
Program
Special
V/f 5-Point Setting
The
V/f 5-Point 5 Voltage
establishes the output voltage level that is to be
associated with the frequency setting of
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
for additional information on this setting.
Direct Access Number — F199
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — V or % (
)
Units — V or % (
)
Frequency Priority Selection
Program
Fundamental
Standard Mode Selection
Either
Frequency Mode 1
(
) or
Frequency Mode 2
) may control
the output frequency of the ASD. This parameter determines which of the two
will control the output frequency and the conditions in which control will be
switched from one to the other.
The
Frequency Source 1
or
Frequency Source 2
selection specifies the source
of the input frequency command signal (Frequency Mode 1 or 2).
Select
Frequency Source 1
for
Frequency Mode 1
control.
Select
Frequency Source 2
for
Frequency Mode 2
control.
If
Frequency Source Priority 1
is selected here, the ASD will follow the
control of the
Frequency Mode 1
setting for the duration that the commanded
frequency of
Frequency Mode 1
is greater than the setting of
. If the
commanded frequency of
Frequency Mode 1
is less than or equal to the setting
of
, the ASD will follow the setting of
Frequency Mode 2
.
If
Frequency Source Priority 2
is selected here, the ASD will follow the
control of the
Frequency Mode 2
setting for the duration that the commanded
frequency of
Frequency Mode 2
is greater than the setting of
. If the
commanded frequency of
Frequency Mode 2
is less than or equal to the setting
of
, the ASD will follow the setting of
Frequency Mode 1
.
If
Frequency Source Priority Switching
is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of
Terminal
Frequency Priority
. The discrete terminal
Terminal Frequency Priority
will
toggle control to and from the
Frequency Mode 1
and
Frequency Mode 2
selections for the duration of each activation/deactivation.
Settings:
0 — Frequency Source 1
1 — Frequency Source 2
2 — Frequency Source 1 Priority
3 — Frequency Source 2 Priority
4 — Frequency Source Priority Switching
Direct Access Number — F200
Parameter Type —
Selection List
Factory Default —
Frequency Source 1
Changeable During Run —
Yes
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......