GX7R ASD Quick Start Guide
37
Monitor Screen
The
Monitor
mode allows the user to monitor
GX7R ASD
/motor performance variables, ASD control
settings, and configuration data during motor operation. The monitored parameters are listed and
described below.
Note:
The
Monitor
mode is a read-only mode. The settings
cannot
be changed from the
Monitor
mode. For information on how to change the values, see the section titled
Default Setting Changes on pg. 33
.
Running Frequency
— Displays the
Output Frequency
.
Frequency Reference
— Displays the
Frequency Setpoint
.
Output Current
— Displays the
Output Current
of the ASD as a percentage of the rated capacity
of the GX7R.
Bus Voltage
— Displays the
Bus Voltage
as a percentage of the rated capacity of the GX7R.
Output Voltage
— Displays the
Output Voltage
as a percentage of the rated capacity of the GX7R.
Discrete Input Terminal Status
— Displays the status of the discrete input terminals of the
Control Terminal Strip
.
OUT1 OUT2 FL
— Displays the status of the discrete output terminals of the
Control Terminal
Strip
.
Timer
— Displays the
Cumulative Run Time
in hours.
Postcomp Frequency
— Displays the
Output Frequency
after the application of the slip
compensation correction value.
Feedback (inst.)
— Provides a status of the
Real Time Feedback
in Hz.
Feedback (1 second)
— Provides a status of the
1-Second Averaging
feedback in Hz.
Torque
—
Displays the
Output Torque
as a percentage of the rated capacity of the GX7R.
Torque Reference
—
Displays the
Torque Reference
as a percentage.
Torque Current
—
Displays the current being used to produce torque.
Excitation Current
—
Displays the current required to produce the excitation field.
PID Value
—
Displays the
PID
feedback
value in Hz (Proportional-Integral-Derivative).
Motor Overload
—
Displays the
Motor Overload
value as a percentage of the rated capacity of the
motor.
ASD Overload
— Displays the
ASD Overload
as a percentage of the rated capacity of the GX7R.
DBR Overload
— Displays the
DBR Overload
value as a percentage of the
Dynamic Braking
Resistor
capacity.
Motor Load
— Displays the
Motor Load
in real time as a percentage of the rated capacity of the
motor.
ASD Load
— Displays the
ASD Load
as a percentage of the rated capacity of the GX7R.
Monitor
Screen
Monitor
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...