GX7R ASD Quick Start Guide
33
Operation
(Local)
Note:
See
F003
for information on
Remote
operation.
To turn the motor on, perform the following:
1. Press the
MON/PRG
key until the
Frequency Command
screen is
displayed.
2. Press the
Local|Remote
key to enter the
Local
mode (green
Local|Remote
LED
illuminates).
3. Turn the
Rotary Encoder
clockwise
until the
Frequency Command
value is
at the desired setting.
4. Press the
Run
key and the motor runs at the
value.
Note:
The speed of the motor may be changed while the motor is running by using the
Rotary
Encoder
to change the
Frequency Command
value.
5. Press the
Stop|Reset
key to stop the motor.
Default Setting Changes
To change a default parameter setting, go to the root of the
Program
menu and turn the
Rotary Encoder
until the desired parameter group is within the cursor block and press the
Rotary Encoder
(repeat if there
is a submenu).
Press the
Rotary Encoder
to select the default setting to be changed and the selection takes on the reverse
video format (dark background, light text). Turn the
Rotary Encoder
to change the value of the
parameter. Press the
ESC
key before accepting the change to exit the menu without saving the change or
press the
Rotary Encoder
to accept the new setting.
For a complete listing of the
Program
mode menu options, see the section titled
. Menu items are listed and mapped for convenience. The
Direct Access Numbers
are listed where applicable.
The default settings may also be changed by entering the
Parameter Number
of the setting to be changed
at the
Direct Access
menu field (Program
Direct Access
applicable parameter number
). A listing of
the
Direct Access/Parameter Numbers
and a description of the associated parameter may be found in
the
GX7R ASD Install and Op Manual
.
A listing of all parameters that have been changed from the factory default setting may be viewed
sequentially by accessing the
Changed From Default
screen (Program
Utility Parameters
Changed
From Default).
Note:
Parameter
F201
was changed to create the example shown below in
The
Changed From Default
feature allows the user to view (or change) the parameters that are different
from the default or the post-reset settings. Once the
Changed From Default
screen is displayed, the
system automatically scrolls through all of the system parameters and halts once reaching a changed
parameter.
The
Rotary Encoder
may be clicked once clockwise to continue scrolling forward or clicked once
counterclockwise to begin scrolling in reverse. With each click of the
Rotary Encoder
from a stop, the
system scrolls through the parameters and stops at the next parameter that has been changed.
Pressing the
Rotary Encoder
while a changed parameter is displayed accesses the settings of the changed
parameter for viewing or changing.
Frequency
Command
0 . 0
FRQ CMD
Run Frq: 0.00Hz
Hz
REM
Out Cur: 0.00%
0 . 0
Frequency Command Screen
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...