GX7R ASD Quick Start Guide
Installation Precautions
Location and Ambient Requirements
•
The TIC ASD is intended for permanent installations only.
•
Installation shall conform to the
National Electrical Code
(NEC)
— Article 110
(
Requirements
For Electrical Installations
), all regulations of the
Occupational Safety and Health
Administration
, and any other applicable national, regional, or industry codes and standards.
Note:
For ALL references to the National Electrical Code (NEC), see the latest release of
the National Electrical Code.
•
Select a mounting location that is easily accessible, has adequate personnel working space, and
adequate illumination for adjustment, inspection, and maintenance of the equipment (refer to the
NEC Article 110-13).
•
DO NOT
mount the ASD in a location that would produce catastrophic results if it were to become
dislodged from its mounting location (equipment damage or injury).
•
DO NOT
mount the ASD in a location that would allow it to be exposed to flammable chemicals or
gases, water, solvents, explosive/corrosive mists or gases, or other fluids.
•
Avoid installation in areas where vibration, heat, humidity, dust, fibers, metal particles, or sources
of electrical noise are present.
•
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to
the section titled
Installation and Connections on pg. 10
for further information on ventilation
requirements.
•
The ambient operating temperature range of the
GX7R ASD
is 14° to 104° F (-10° to 40° C).
Note:
Derate the applicable rating by one percent for each degree Celsius above the rated
thermal operating capacity.
Mounting Requirements
•
Only
Qualified Personnel
shall install this equipment.
•
Unit is to be securely installed on the floor in an upright position in a well-ventilated area.
•
As a minimum, the installation of the equipment shall conform to the
NEC — Article 110
(NEC),
OSHA, as well as any other applicable national, regional, or industry codes and standards.
•
Installation practices shall conform to the latest revision of NFPA 70E Electrical Safety
Requirements for Employee Workplaces.
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...