Press
the ENTER (= Y) key to change settings and return to the " Prot. element" screen.
Setting the ZPS protection
•
Select "ZPS prot." to display the "ZPS prot." screen.
/ 7 Z P S p r o t .
Z P S 1 V ZPS1
Threshold
setting.
2 0 . 0 _
T Z P S 1
1 0 . 0 0
ZPS1 Time multiplier setting. Display if [ZPS1EN]
= 2 or 3.
T Z P S 1 s
0 . 0 0
ZPS1 Definite time setting. Display if [ZPS1EN]=
1.
T Z P S 1 R s
0 . 0
ZPS1 Definite time reset delay. Display if
[ZPS1EN] = 2 or 3.
Z P S 2 V ZPS2
Threshold
setting.
4 0 . 0
T Z P S 2
0 . 0 0
ZPS2 Time multiplier setting. Display if [ZPS2EN]
= 2 or 3.
T Z P S 2 s
0 . 0 0
ZPS2 Definite time setting. Display if [ZPS2EN]=
1.
T Z P S 2 R s
0 . 0
ZPS2 Definite time reset delay. Display if
[ZPS2EN] = 2 or 3.
Z P S 1 - k IDMT
curve
setting
of
ZPS1
1 . 0 0
Z P S 1 -
α
IDMT curve setting of ZPS1
1 . 0 0
Z P S 1 - c IDMT
curve
setting
of
ZPS1
0 . 0 0 0
Z P S 2 - k IDMT
curve
setting
of
ZPS2
1 . 0 0
Z P S 2 -
α
IDMT curve setting of ZPS2
1 . 0 0
Z P S 2 - c IDMT
curve
setting
of
ZPS2
0 . 0 0 0
•
Enter the numerical value and press the ENTER key.
•
After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
•
Press
the ENTER (= Y) key to change settings and return to the " Prot. element" screen.
Setting the NPS protection
•
Select "NPS prot." to display the "NPS prot." screen.
/ 7 N P S p r o t .
N
P S 1 V NPS1
Threshold
setting.
2 0 . 0 _
T N P S 1
1 0 . 0 0
NPS1 Time multiplier setting. Display if [NPS1EN]
= 2 or 3.
T N P S 1 s
0 . 0 0
NPS1 Definite time setting. Display if [NPS1EN]=
1.
Summary of Contents for GRD130-210
Page 112: ... 111 6 F 2 S 0 7 5 7 Appendix A Signal List ...
Page 116: ... 115 6 F 2 S 0 7 5 7 Appendix B Event Record Items ...
Page 120: ... 119 6 F 2 S 0 7 5 7 Appendix C Binary Output Default Setting List ...
Page 122: ... 121 6 F 2 S 0 7 5 7 Appendix D Details of Relay Menu ...
Page 134: ... 133 6 F 2 S 0 7 5 7 Appendix E Case Outline ...
Page 136: ... 135 6 F 2 S 0 7 5 7 Appendix F Typical External Connection ...
Page 151: ... 150 6 F 2 S 0 7 5 7 ...
Page 156: ... 155 6 F 2 S 0 7 5 7 Appendix I Return Repair Form ...
Page 160: ... 159 6 F 2 S 0 7 5 7 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 161: ... 160 6 F 2 S 0 7 5 7 ...
Page 162: ... 161 6 F 2 S 0 7 5 7 Appendix J Technical Data ...
Page 167: ... 166 6 F 2 S 0 7 5 7 ...
Page 168: ... 167 6 F 2 S 0 7 5 7 Appendix K Symbols Used in Scheme Logic ...
Page 171: ... 170 6 F 2 S 0 7 5 7 ...
Page 172: ... 171 6 F 2 S 0 7 5 7 Appendix L IEC60870 5 103 Interoperability ...
Page 180: ... 179 6 F 2 S 0 7 5 7 Appendix M Ordering ...
Page 183: ......