73
6
F
2
S
0
7
5
7
•
Enter 0 (=ALM&BLK) to alarm and to block the tripping if detecting the AC input imbalance
and press the ENTER key. If alarming only, enter 1 (=ALM) and press the ENTER key.
Setting the OV protection
•
Select "OV prot." on the "Scheme sw" screen to display the "OV prot." screen.
/ 7 O
V p r o t .
O V 1 E N 0 _
O f f / D T / I D M T / C
O V 2 E N 0
O f f / D T / I D M T / C
O V 3 E N 0
O f f / O n
<
OV1EN, OV2EN
>
To set the OV1 or OV2 delay type, do the following.
•
Enter 1 (=DT) or 2 (=IDMT) or 3 (=C) and press the ENTER key. If disabling the OV1 or
OV2, enter 0 (=Off) and press the ENTER key.
<
OV3EN
>
•
Enter 1 (=On) to enable the OV3 and press the ENTER key. If disabling the OV3, enter 0
(=Off) and press the ENTER key.
•
After setting, press the END key to display the following confirmation screen.
C h a n g e s e t t i n g s ?
E N T E R = Y C A N C E L = N
•
Press
the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
Setting the UV protection
•
Select "UV prot." to display the "UV prot." screen.
/ 7 U
V p r o t .
U V 1 E N 1 _
O f f / D T / I D M T / C
U V 2 E N 0
O f f / D T / I D M T / C
U V 3 E N 0
O f f / O n
V B L K E N
0
O f f / O n
<
UV1EN, UV2EN
>
To set the UV1 or UV2 delay type, do the following.
•
Enter 1 (=DT) or 2 (=IDMT) or 3(=C) and press the ENTER key. If disabling the UV1 or
UV2, enter 0 (=Off) and press the ENTER key.
Summary of Contents for GRD130-210
Page 112: ... 111 6 F 2 S 0 7 5 7 Appendix A Signal List ...
Page 116: ... 115 6 F 2 S 0 7 5 7 Appendix B Event Record Items ...
Page 120: ... 119 6 F 2 S 0 7 5 7 Appendix C Binary Output Default Setting List ...
Page 122: ... 121 6 F 2 S 0 7 5 7 Appendix D Details of Relay Menu ...
Page 134: ... 133 6 F 2 S 0 7 5 7 Appendix E Case Outline ...
Page 136: ... 135 6 F 2 S 0 7 5 7 Appendix F Typical External Connection ...
Page 151: ... 150 6 F 2 S 0 7 5 7 ...
Page 156: ... 155 6 F 2 S 0 7 5 7 Appendix I Return Repair Form ...
Page 160: ... 159 6 F 2 S 0 7 5 7 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 161: ... 160 6 F 2 S 0 7 5 7 ...
Page 162: ... 161 6 F 2 S 0 7 5 7 Appendix J Technical Data ...
Page 167: ... 166 6 F 2 S 0 7 5 7 ...
Page 168: ... 167 6 F 2 S 0 7 5 7 Appendix K Symbols Used in Scheme Logic ...
Page 171: ... 170 6 F 2 S 0 7 5 7 ...
Page 172: ... 171 6 F 2 S 0 7 5 7 Appendix L IEC60870 5 103 Interoperability ...
Page 180: ... 179 6 F 2 S 0 7 5 7 Appendix M Ordering ...
Page 183: ......