162
6
F
2
S
0
7
5
7
TECHNICAL DATA
Ratings
AC voltage V
n
: 110V
Frequency: 50Hz
or
60Hz
DC auxiliary supply:
110/125Vdc (Operative range: 88 - 150Vdc)
220/250Vdc (Operative range: 176 - 300Vdc)
48/54/60Vdc (Operative range: 38.4 - 72Vdc)
Superimposed AC ripple on DC supply:
maximum 12%
DC supply interruption:
maximum 50ms at 110V
Binary input circuit DC voltage:
110/125Vdc (Operative range: 88 - 150Vdc)
220/250Vdc (Operative range: 176 - 300Vdc)
48/54/60Vdc (Operative range: 38.4 - 72Vdc)
Overload Ratings
AC voltage inputs:
2 times rated voltage continuous
Burden
AC phase voltage inputs:
≤
0.1VA (at rated voltage)
DC power supply:
≤
10W (quiescent),
≤
15W (maximum)
Binary input circuit:
≤
0.5W per input at 110Vdc
Overvoltage Protection
1
st
, 2
nd
, 3
rd
Overvoltage thresholds:
OFF, 10.0 – 200.0V in 0.1V steps
Delay type (1
st
, 2
nd
threshold): DTL,
IDMTL
IDMTL Time Multiplier Setting TMS:
0.05 - 100.00 in 0.01 steps
DTL delay:
Inst, 0.01 - 300.00s in 0.01s steps
DO/PU ratio
10 - 98% in 1% steps
Reset Delay (1
st
, 2
nd
threshold and IDMTL):
Instantaneous, 0.1 – 300.0s in 0.1s steps
Undervoltage Protection
1
st
, 2
nd
, 3
rd
Undervoltage thresholds:
OFF, 5.0 – 130.0V in 0.1V steps
Delay type (1
st
, 2
nd
threshold): DTL,
IDMTL
IDMTL Time Multiplier Setting TMS:
0.05 - 100.00 in 0.01 steps
DTL delay:
Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (1
st
, 2
nd
threshold and IDMTL):
Instantaneous, 0.1 – 300.0s in 0.1s steps
Zero Sequence Overvoltage (ZPS) Protection
1
st
, 2
nd
ZPS Overvoltage thresholds:
OFF, 1.0 – 160.0V in 0.1V steps
Delay type:
DTL, IDMTL
IDMTL Time Multiplier Setting TMS:
0.05 - 100.00 in 0.01 steps
DTL delay:
Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (IDMTL):
Instantaneous, 0.1 – 300.0s in 0.1s steps
Negative Sequence Overvoltage (NPS) Protection
1
st
, 2
nd
NPS Overvoltage thresholds:
OFF, 1.0 – 160.0V in 0.1V steps
Delay type:
DTL, IDMTL
IDMTL Time Multiplier Setting TMS:
0.05 - 100.00 in 0.01 steps
DTL delay:
Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (IDMTL):
Instantaneous, 0.1 – 300.0s in 0.1s steps
Summary of Contents for GRD130-210
Page 112: ... 111 6 F 2 S 0 7 5 7 Appendix A Signal List ...
Page 116: ... 115 6 F 2 S 0 7 5 7 Appendix B Event Record Items ...
Page 120: ... 119 6 F 2 S 0 7 5 7 Appendix C Binary Output Default Setting List ...
Page 122: ... 121 6 F 2 S 0 7 5 7 Appendix D Details of Relay Menu ...
Page 134: ... 133 6 F 2 S 0 7 5 7 Appendix E Case Outline ...
Page 136: ... 135 6 F 2 S 0 7 5 7 Appendix F Typical External Connection ...
Page 151: ... 150 6 F 2 S 0 7 5 7 ...
Page 156: ... 155 6 F 2 S 0 7 5 7 Appendix I Return Repair Form ...
Page 160: ... 159 6 F 2 S 0 7 5 7 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 161: ... 160 6 F 2 S 0 7 5 7 ...
Page 162: ... 161 6 F 2 S 0 7 5 7 Appendix J Technical Data ...
Page 167: ... 166 6 F 2 S 0 7 5 7 ...
Page 168: ... 167 6 F 2 S 0 7 5 7 Appendix K Symbols Used in Scheme Logic ...
Page 171: ... 170 6 F 2 S 0 7 5 7 ...
Page 172: ... 171 6 F 2 S 0 7 5 7 Appendix L IEC60870 5 103 Interoperability ...
Page 180: ... 179 6 F 2 S 0 7 5 7 Appendix M Ordering ...
Page 183: ......