6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 962 -
5.6.2
LED Indicators
The LED indicators #1 and #2 are used to indicate the IED statuses. The others (#3 to #26) are
provided to indicate statuses, which the user wishes to check; the settings or by the PLC
function can control to indicate the statuses. The user can make a new indicator label using
the label maker of the GR-TIEMS®. (See
Chapter Engineering tool
)
The LED indicators‡ (#3 to #26) are also provided as user-programmable indicators.
Figure 5.6-2 shows the schematic diagrams. Each LED indicator can be lit and controlled using
a logic-gate-switch setting and others. For simplicity, we discuss setting the LED indicator #3
only, but the user can take account that setting the other LED indicators (#4 to #26) is the
same as the #3. Table 5.6-1 shows the LED indicator settings; Table 5.6-2 shows the signal
monitoring points on all LED indicator logics.
‡Note: Setting menus of the LED indicator are also discussed in Chapter
User interface:
I/O setting sub-menu.
(i)
Selection of input signals
The LED indicator (#3) is lit by entering signals from other functions; eight ports are provided
for the entering signals, designated as
input-signal1
to
input-signal8
. The user should ensure
one or more DataIDs are set for the
input-signal1
to
input-signal8
. Entering signals are
designated using DataIDs, respectively; the user should set respective DataIDs for the settings
[
Input signal1
] to [
Input signal8
].
(ii)
Logic gate switch
In the LED indicator logic #3 a logic scheme is provide for the eight entering signals; the
entering signals are grouped by the selection using scheme switch [
LOGIC-SW
] for which the
user should set either
AND
,
OR
or
XOR
.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......