Guide Specification – 3-Phase Static Uninterruptible Power Supply
15
9.1.2
HTTP Familiarity
The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS
information from any machine with a web browser. At any time, a network workstation or
management station shall be able to open a RemotEye II website. RemotEye II website shall
enable the UPS system information to be configured and monitored remotely. RemotEye II
shall provide access to 3 java applets for monitoring, event logging, and trend analysis.
9.1.3
Shutdown Capability
The RemotEye II application software shall allow RemotEye II to remotely notify and
shutdown selected network servers.
Network Adapter/External Hardware
AMD 188ES-20MHz
512kB SRAM: 512kB Flash
Two asynchronous serial ports
10 BaseT RJ-45 connector
Toshiba UPS communication protocol
SNMP over UDP/IP : HTTP over TCP/IP:ARP, RARP, TFTP and
ICMP
MIB_II : Toshiba v1.2_MIB :JEM MIB : RFC 1628
Traffic LED for network : Status LED for status : Power LED for
Power
2 digit (default setting is Switches 1 and 2 off)
Temperature Range: 0 – 40 C
Relative Humidity: 10 – 80 %
Power Requirements: 12 VDC ungrounded
2.0 Watts Maximum
Dimensions: 5.28”(134mm) x 3.40”(86mm) x 1.10”(27mm) (LxWxH)
Weight: 0.38lbs(170g)
Certifications: FCC class A, UL, CUL, CE
9.2
Remote Status Alarm Panel (RSAP)
The manufacturer shall optionally provide a RSAP that shall provide a wall-mounted LED mimic
display for UPS status events of:
Input ON
Bypass ON
Inverter ON
Low Battery, AC Fail
New alarm annunciation
Battery backup for the RSAP monitor.