63
G8000 Series Installation and Operation Manual
14.3 Startup Procedures
The procedure to start the UPS is shown in Steps 1-5.
STEP 1
Turn on the control power supply switch.
(Figure 14.1) and ensure the operation lock is
set to OPERATION. (Figure 13.1 - 1)
STEP 2
Wait for a few seconds.
STEP 3
Press the “RUN” button for at least 0.5
seconds.
CONVERTER LED is “ON” and INVERTER
LED flashes.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
SYSTEM INITIALIZE
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
PRESS ‘RUN’ SWITCH
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
UPS STARTING
WAIT FOR A WHILE
LED Key
- LED Off
- LED On
- LED Flash