G8000 Series Installation and Operation Manual
TABLE 11.2 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 100 KVA UPS
Block Number
Cable Size (Min-Max)
2
Tightening Torque
75 °C Copper Wire
90 °C Copper Wire
1
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
2
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
3
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
4
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
5
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
6
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
7
3
(2) 2/0 AWG
(2) 2/0 AWG
50 in.-lb. (5.6 N•m)
8
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
9
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
10
(2) #1 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
11
3
(2) 2/0 AWG
(2) 2/0 AWG
50 in.-lb. (5.6 N•m)
12
1,2
(2) 3/0 - (2) 4/0 AWG
(2) 2/0 - (2) 3/0 AWG
325 in.-lb. (36.7 N•m)
13
1,2
(2) 3/0 - (2) 4/0 AWG
(2) 2/0 - (2) 3/0 AWG
325 in.-lb. (36.7 N•m)
1
One battery string. (Consult factory if using more than one battery string.)
2
Maximum cable size for terminal lugs 1-11: 2 x 6 to 2/0 AWG; Battery Terminals 12-13: 2 x 6 AWG to 350 kcmil.
3
Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.
TABLE 11.2 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 125 KVA UPS
Block Number
Cable Size (Min-Max)
2
Tightening Torque
75 °C Copper Wire
90 °C Copper Wire
1
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
2
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
3
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
4
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
5
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
6
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
7
3
(2) 2/0 AWG
(2) 2/0 AWG
50 in.-lb. (5.6 N•m)
8
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
9
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
10
(2) #3 – (2) 2/0 AWG
2/0 – (2) 2/0 AWG
50 in.-lb. (5.6 N•m)
11
3
(2) 2/0 AWG
(2) 2/0 AWG
50 in.-lb. (5.6 N•m)
12
1,2
(2) 3/0 - (2) 4/0 AWG
(2) 2/0 - (2) 3/0 AWG
325 in.-lb. (36.7 N•m)
13
1,2
(2) 3/0 - (2) 4/0 AWG
(2) 2/0 - (2) 3/0 AWG
325 in.-lb. (36.7 N•m)
1
One battery string. (Consult factory if using more than one battery string.)
2
Maximum cable size for terminal lugs 1-11: 2 x 6 to 2/0 AWG; Battery Terminals 12-13: 2 x 6 AWG to 350 kcmil.
3
Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.
Summary of Contents for G8000 Series
Page 2: ......
Page 10: ...iv G8000 Series Installation and Operation Manual ...
Page 88: ...78 G8000 Series Installation and Operation Manual ...
Page 110: ...100 G8000 Series Installation and Operation Manual ...
Page 113: ...103 G8000 Series Installation and Operation Manual FIGURE B 3 G8000 300 KVA OUTLINE DRAWING ...
Page 114: ...104 G8000 Series Installation and Operation Manual FIGURE B 4 G8000 500 KVA OUTLINE DRAWING ...
Page 119: ......