Direct Access Parameter Information
https://www.toshiba.com/tic/
85
Low-Speed Signal Output Frequency
Program
Terminal
Reach Settings
The Low-Speed Signal Output Frequency parameter sets an
ASD output frequency threshold that activates the assigned dis
-
crete output terminal for the duration that the ASD output speed
is equal to or less than this setting.
Direct Access Number —
F100
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
Units — Hz
Speed Reach Frequency
Program
Terminal
Reach Settings
The Speed Reach Frequency sets a frequency threshold that,
when reached or is within the bandwidth specified by parameter
, activates the assigned discrete output terminal for the
duration that the ASD output is within the
bandwidth.
Direct Access Number —
F101
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
Units — Hz
Speed Reach Detection Band
Program
Terminal
Reach Settings
This parameter sets the bandwidth of the Speed Reach Fre
-
quency
setting.
Direct Access Number —
F102
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
Units — Hz
Forward/Reverse Run Priority When Both Are Closed
Program
Terminal
Input Special Functions
The Forward/Reverse Priority Selection determines the operation
of the ASD if the F and R control terminals are activated simulta
-
neously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combina
-
tions of the F and R terminal settings if the Reverse option is cho
-
sen.
The Suspend setting will decelerate the motor to a stop regard
-
less of the rotation direction when both the F and R control termi
-
nals are activated.
Direct Access Number —
F105
Parameter Type —
Selection List
Factory Default —
Suspend
Changeable During Run —
No
Simultaneous F and R activation.
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......