Direct Access Parameter Information
Deceleration Time 1
Program
Fundamental
Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the
ASD to go from the Maximum Frequency to 0.0 Hz for the Decel
-
eration 1 profile. The Accel/Decel Pattern may be set using
Note: A deceleration time shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings
may lengthen the deceleration times.
Direct Access Number —
F010
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Maximum Frequency
Program
Fundamental
Frequency Settings
This setting determines the absolute maximum frequency that the
ASD can output.
Accel/Decel times are calculated based on the Maximum Fre
-
quency setting.
The Maximum Frequency is not limited by this setting while oper
-
ating in the Drooping Control mode (see
).
Note: This setting may not be lower than the Upper-Limit
Frequency (
setting
.
Direct Access Number —
F011
Parameter Type —
Numerical
Factory Default —
80.00
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
Upper-Limit Frequency
Program
Fundamental
Frequency Settings
This parameter sets the highest frequency that the ASD will
accept as a frequency command or frequency setpoint. The ASD
may output frequencies higher than the Upper-Limit Frequency
(but, lower than the Maximum Frequency) when operating in the
PID Control mode, Torque Control mode, or the Vector Control
modes (sensorless or feedback).
Note: This setting may not be higher than the Maximum
Frequency (
setting or lower than the Lower Limit
setting (
).
Direct Access Number —
F012
Parameter Type —
Numerical
Factory Default —
66.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Lower-Limit Frequency
Program
Fundamental
Frequency Settings
This parameter sets the lowest frequency that the ASD will
accept as a frequency command or frequency setpoint. The ASD
will output frequencies lower than the Lower-Limit Frequency
when accelerating to the lower limit or decelerating to a stop. Fre
-
quencies below the Lower Limit may also be output when operat
-
ing in the PID Control mode, Torque Control mode, or the Vector
Control modes (sensorless or feedback).
Note: This setting may not be higher than the Upper Limit
Frequency (
setting.
Direct Access Number —
F013
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......