Direct Access Parameter Information
https://www.toshiba.com/tic/
185
Low-Current Detection Current Hysteresis Width
Program
Protection
Low-Current Settings
During a momentary low-current condition, this parameter pro
-
vides a current threshold level to which the low-current condition
must return within the time setting of
will be incurred.
Direct Access Number —
F609
Parameter Type —
Numerical
Factory Default —
10
Changeable During Run —
Yes
Minimum — 1
Maximum — 20
Units — %
Low-Current Trip
Program
Protection
Low-Current Settings
This parameter Enables/Disables the low-current trip feature.
When enabled, the ASD will trip on a low-current fault if the out
-
put current of the ASD falls below the level defined at
and
remains there for the time set at
.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number —
F610
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Low-Current Detection Current
Program
Protection
Low-Current Settings
With the Low-Current Trip (
) parameter enabled, this func
-
tion sets the low-current trip threshold.
The threshold value is entered as a percentage of the maximum
rating of the ASD.
Direct Access Number —
F611
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Low-Current Detection Time
Program
Protection
Low-Current Settings
With the Low-Current Trip (
) parameter enabled, this func
-
tion sets the time that the low-current condition must exist to
cause a trip.
Direct Access Number —
F612
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Units — Seconds
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......