Direct Access Parameter Information
RR Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the RR input ter
-
minal when this terminal is used as the control input while operat
-
ing in the Speed Control mode or the Torque Control mode.
This setting may be used to ensure that the 100% level of the
input source (pot, pressure transducer, flow meter, etc.) is also
the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and
adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number —
F473
Parameter Type —
Numerical
Factory Default —
154
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the RX input ter
-
minal when this terminal is used as the control input while operat
-
ing in the Speed Control mode or the Torque Control mode.
This setting may be used to ensure that the zero level of the input
source (pot, pressure transducer, flow meter, etc.) is also the zero
level setting of the ASD system.
This is accomplished by setting the input source to zero and
adjusting this setting to provide an output of zero from the ASD.
Direct Access Number —
F474
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the gain of the RX input ter
-
minal when this terminal is used as the control input while operat
-
ing in the Speed Control mode or the Torque Control mode.
This setting may be used to ensure that the 100% level of the
input source (pot, pressure transducer, flow meter, etc.) is also
the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and
adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number —
F475
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX2 Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the RX2 (AI1
Option) input terminal when this terminal is used as the control
input while operating in the Speed Control mode or the Torque
Control mode.
This setting may be used to ensure that the zero level of the input
source (pot, pressure transducer, flow meter, etc.) is also the zero
level setting of the ASD system.
This is accomplished by setting the input source to zero and
adjusting this setting to provide a zero output from the ASD.
Direct Access Number —
F476
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......