Direct Access Parameter Information
https://www.toshiba.com/tic/
145
Commercial Power/ASD Switching Frequency
Program
Terminal
Line Power Switching
F354 and with a properly configured discrete
output terminal
, this parameter sets the frequency at which the At
Frequency Powerline Switching function engages.
The At Frequency Powerline Switching function commands the
system to discontinue using the output of the ASD and to switch
to commercial power once reaching the frequency set here.
for additional information on this parameter.
Direct Access Number —
F355
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
Units — Hz
ASD Side-Switching Delay Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will
wait before outputting a signal to the motor once the switch-to-
ASD-output criteria has been met.
for additional information on this parameter.
Direct Access Number —
F356
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Commercial Power Side Switching Delay Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the ASD will
wait before allowing commercial power to be applied to the motor
once the switch-to-commercial-power criteria has been met.
for additional information on this parameter.
Direct Access Number —
F357
Parameter Type —
Numerical
Factory Default —
0.62
Changeable During Run —
Yes
Minimum — 0.40
Maximum — 10.00
Units — Seconds
Commercial Power Switching Freq. Hold Time
Program
Terminal
Line Power Switching
This parameter determines the amount of time that the connec
-
tion to commercial power is maintained once the switch-to-ASD-
output criteria has been met.
for additional information on this parameter.
Direct Access Number —
F358
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......