Direct Access Parameter Information
https://www.toshiba.com/tic/
127
Jog Frequency
Program
Frequency
Jog Settings
This parameter sets the output frequency of the ASD during a
Jog. Jogging is the term used to describe turning on the motor for
small increments of time and is used when precise positioning of
motor-driven equipment is required.
The Jog function is initiated via the Terminal Board or using Com
-
munications (see the Communications manual-P/N 53840 for
additional information on using Communications for Jogging).
The Jog function can be activated from zero Hz or from any fre
-
quency below the Jog Run Frequency setting (Jog can only
increase the speed). A Jog command will not be recognized
when the running frequency is above the Jog Run Frequency set
-
ting. The Jog command has priority over other Run commands
and is not limited by the Upper-Limit setting of parameter
.
Jog commands received for the opposite direction of the com
-
manded frequency will follow the programmed stopping method
of
until reaching zero Hz and will then ramp to the pro
-
grammed Jog Frequency and direction.
Jog Setup and Execution
To initiate a Jog Run from the EOI perform the following:
7. Set the Command Mode Selection (
) to EOI Keypad.
This setting places the ASD in the Remote mode.
8.Set the Frequency Mode Selection (
) to EOI Keypad.
9.Enable the Jog function (
).
10.Set the Input Terminal Priority (
) function to Enable to
receive Jog commands.
11.Assign the Jog Run setting to any unused discrete input ter
-
).
12.Set the Jog Frequency at
13.Set up a Jog Stop Pattern at
.
14.Press the Run key and the ASD will output the commanded
frequency (as programmed; not the Jog frequency).
15.Activate the Jog Run terminal (from step
). The ASD will
output the Jog frequency setting of
) for the
duration of the activation.
16.Stop the Jog by either providing a Stop command or termi
-
nating the Jog Run terminal activation. Providing a Stop com
-
mand will terminate the commanded frequency and the Jog
function. Terminating the Jog Run terminal activation will ter
-
minate the Jog function only and will resume the commanded
frequency of step
Direct Access Number —
F260
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — Start Frequency
(
)
Maximum — (ASD-Dependent)
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......