Direct Access Parameter Information
https://www.toshiba.com/tic/
123
Start Frequency
Program
Special
Frequency Control
The output of the ASD will remain at 0.0 Hz until the pro
-
grammed speed value exceeds this setting during start up. Once
exceeded during start up, the output frequency of the ASD will
accelerate to the programmed setting.
Output frequencies below the Start Frequency will not be output
from the ASD during start up. However, once reaching the Start
Frequency, speed values below the Start Frequency may be out
-
put from the ASD.
If the setting of this parameter results in an over-current condi
-
tion at start up, reduce the setting of this parameter to a value
less than the rated slippage of the motor.
If zero-speed torque is required, set this parameter and
0.0 Hz.
This setting will override the setting of
higher value.
This parameter setting is used during a Jog as the Lower-Limit
Frequency (see
).
Direct Access Number —
F240
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
Run Frequency
Program
Special
Frequency Control
This parameter establishes a center frequency (Run Frequency)
of a frequency band.
provides a plus-or-minus value for the Run Fre
-
quency; thus, establishing a frequency band.
During acceleration, the ASD will not output a signal to the motor
until the lower level of the band is reached.
During deceleration, the ASD will continue to output the pro
-
grammed deceleration signal to the motor until the lower level of
the band is reached; at which time the output will go to 0.0 Hz.
Direct Access Number —
F241
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Run Frequency Hysteresis
Program
Special
Frequency Control
This parameter provides a plus-or-minus value for the Run Fre
-
quency setting
.
Direct Access Number —
F242
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......