RX2 Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RX2 Input Point 1 Frequency and is the fre
-
quency that is associated with the setting of RX2 Input Point 1
Setting when operating in the Speed Control mode.
See RX2 Input Point 1 Setting (
) for additional information
on this parameter.
Direct Access Number —
F223
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
RX2 Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the RX2 input level that is associated with
RX2 Input Point 2 Frequency
when operating in the Speed con
-
trol mode or is associated with the RX2 Input Point 2 Rate when
operating in the Torque Control mode.
This value is entered as -100% to +100% of the RX2 input signal
range.
See RX2 Input Point 1 Setting (
) for additional information
on this parameter when used for Speed control.
Direct Access Number —
F224
Parameter Type —
Numerical
Factory Default —
+100
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
RX2 Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RX2 Input Point 2 Frequency and is the fre
-
quency that is associated with the setting of RX2 Input Point 2
Setting when operating in the Speed Control mode.
See RX2 Input Point 1 Setting (
) for additional information
on this parameter.
Direct Access Number —
F225
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......