Direct Access Parameter Information
https://www.toshiba.com/tic/
97
Input Terminal 13 – 20 Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in
the 13 – 20
terminal inputs by the programmed value (see wave
-
).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number —
F145
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 5
Maximum — 200
Units — mS
Output Terminal 10 (R3) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the R3
output terminal to
any one of the user-selectable functions listed in
.
In addition, the output terminals must be specified as Normally
Open or Normally Closed.
See the instruction manual for the 16-Bit BIN/BCD option for
additional information on the function of this terminal.
Direct Access Number —
F168
Parameter Type —
Selection List
Factory Default —
Always OFF
Changeable During Run —
No
Output Terminal 11 (R4) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the R4
output terminal to
any one of the user-selectable functions listed in
.
In addition, the output terminals must be specified as Normally
Open or Normally Closed.
See the instruction manual for the 16-Bit BIN/BCD option for
additional information on the function of this terminal.
Direct Access Number —
F169
Parameter Type —
Selection List
Factory Default —
Always
OFF
Changeable During Run —
No
Base Frequency 2
Program
Motor
Motor Set 2
The Base Frequency 2
setting is the frequency at which the out
-
put voltage of the ASD reaches its maximum setting. The Base
Frequency Voltage 2
This parameter is used only when the parameters for Motor Set 2
are configured and selected. Motor Set 2 may be selected by a
properly configured input terminal (see
).
For proper motor operation, the Base Frequency should be set
for the nameplated frequency of the motor.
Direct Access Number —
F170
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......