2.3. DeviceNet
indicators (Status LED)
MS (Module status)
This bi–color (green/red) LED indicates the status of the communication link from
DEV001Z to the VF-S11. It indicates whether or not the device has power and is operating
properly. (According to ODVA DeviceNet Specifications.)
NS (Network status)
This bi–color (green/red) LED indicates the status of the communication link from the
DEV001Z to DeviceNet. (According to ODVA DeviceNet Specifications.)
LED is:
For this state:
To indicate:
Off
Power OFF
There is no power applied to the device.
Green
Device Operational
The device is operating in a normal condition.
Flashing Green
Device in Standby
The device needs commissioning due to configuration missing,
incomplete or incorrect.
* When a setup of the parameter
f890
-
f894
is outside
the range, it will be in this state.
The Device may be in the Standby state.
Flashing Red
Minor Fault
Recoverable Fault
Red
Unrecoverable Fault
The device has an unrecoverable fault; may need replacing.
Flashing Red-Green
Device Self Testing
The Device is in Self Test.
LED is:
For this state:
To indicate:
Off
Not Powered/Not On–line
Device is not on–line.
- The device has not completed the Dup_MAC_ID test yet.
- The device may not be powered, look at Module Status LED.
Green
On-line and connect
The device is on–line and has connections in the established state.
- The device is allocated to a Master.
Flashing Green
On-line, not connect
Device is connected to the network but has no connections in the
established state.
- The device is not allocated to a master.
Flashing Red
Connection Time-out
Recoverable Fault. One or more I/O Connections are in the
Timed–Out state.
Red
Critical Link Failure
Non Recoverable fault. The device has detected an error that has
rendered it incapable of communicating on the network (Duplicate
MAC ID, or Bus–off). Check parameters
f890
,
f891
then
Cycle power to VF-S11 to reset this fault.