– 22 –
43-EN
44-EN
EN
FR
■
Manual address setting using a remote control
This procedure should be used if the indoor unit wiring is completed and the outdoor unit wiring has not been
started.
For this procedure the group remote control should not be connected. One individual remote control should be used
to set the address on each individual indoor unit (one unit at a time), by wiring the remote control directly to the
indoor unit that is to be addressed.
When the address setting procedure is completed for the individual indoor units the group remote control should
be connected as shown.
CAUTION
Connector
Do not close the connectors between the (U1, U2) and (U3, U4) terminals before completing all refrigerant line
address setting. If a connector is closed the address cannot be set correctly.
▼
Wiring example for 2 refrigerant lines
(Note: the group control of more than two refrigerant systems is possible only when all the FS units are single
port type.)
Refrigerant line 1
Outdoor
unit
Remote
control
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
Outdoor
unit
Refrigerant line 2
Line (system) address
1
1
1
2
2
Indoor unit address
1
2
3
1
2
Group address
1
Header unit
2
Follower unit
2
Follower unit
2
Follower unit
2
Follower unit
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
*The items in bold font must be set manually.
Outdoor unit’s interface
P.C. board
Header unit
Follower unit
Header unit
Follower unit
Header unit
Factory default
SW13, 14 (See chart on
page 20)
(Line (system) address)
1
(No setting
required)
2
(No setting
required)
3
1
DIP switch 2 of SW30 (See
the figure on page 21)
(Terminator of indoor/
outdoor system
interconnecting line and
central control line)
ON
(No setting
required)
Set to OFF
after setting
addresses.
(No setting
required)
Set to OFF
after setting
addresses.
ON
Connector
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
A
U1 U2
U3 U4
U3 U4
U3 U4
U3 U4
U3 U4
U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2
2
U
1
U
2
U
1
U
2
U
1
U
2
U
1
U
2
U
1
U
U5 U6
B
A
B
A
B
A
B
A
B
Header unit 1
Follower unit 1
Follower unit 2
Header unit 2
Header unit 3
Central
control
Connector
Remote
control
Individual
Indoor units
(automatic setting)
Group
Remote
control
Remote
control
Remote
control
Connector
Connector
Line (system) address
1
1
2
2
3
Indoor unit address
1
2
1
2
1
Group address
0
0
1
2
0
1122001101_EN FR.indd 22
1122001101_EN FR.indd 22
6/27/16 4:58 PM
6/27/16 4:58 PM