Modbus interface
Installation Manual
REQUIREMENT
REQUIREMENT
Disconnect the appliance from the main power supply.
This appliance must be connected to the main power supply by a circuit breaker or switch with a contact separation of at least
3 mm.
Fasten the screws to the terminal with torque of 0.5 Nm.
Wiring connection
The following describes a connection example when two or more Modbus interface units are used.
Termination resistance setting (See “6 Setting” for the setting method.)
• Set the RS-485 termination resistance to “120 ohm” for address1 (Modbus interface address SW1=1) Modbus
interface unit, and set to “open” for other units.
• Set the Uh Line Termination resistance.
Refer to "Termination resistance setting"(P.6)
Shield earthing
• The shielded wire of the RS-485 communication cable must be earthed on address 1 (Modbus interface address
SW=1) Modbus interface. Fix the shielded wire of RS-485 communication cable with metal cable clamp and
screw it to the chassis to earth it. The shielded wires must be crimped with closed end connectors on interfaces
with address of other than 1. The shielded wire ends must be insulated and left open.
• Do not connect the shield wire to the terminal block. It should be open and insulated. The shielded wire of the
Uh Line communication cable must be earthed on the air conditioner.
LINK(Uh)
U3
U4 FG
RS-485
L N
SW1
SW4
LED1
LED2
LED3
LED4
LED5
SW2
SW7
SW6
SW5
SW3
1 2 3 4
SG
A(+)
B(-)
SW8
1 2
Air conditioner
Modbus Master
Power supply
220V-240 VAC
(50/60 Hz)
The shielded wire of the RS-485
communication cable must be earthed on
address 1 (Modbus interface address SW=1)
Modbus interface. The shielded wires must
be crimped with closed end connectors on
interfaces with address of other than 1. The
shielded wire ends must be insulated and left
open.
The shielded wire of the Uh
Line communication cable
must be earthed on the air
conditioner. Do not connect
the shield wire to the
terminal block. It should be
open and insulated.
Connect the earth wire to the
earth terminal on the chassis.
Connect the power supply cable
and earth wire to the terminals
using ring terminals with insulation
sleeve.
To connect 2 cables,
change the preset cable
clamp to the provided one
and fix the cables with the
cable clamp as shown in
the figure left.
11-EN