Method 2
If it is not possible to turn on the indoor unit or read the setting data from the P.C. board to be replaced via a wired
remote controller or operate the remote controller due to the failure of its power supply circuit -
Replacing EEPROM (IC10) (For the location of this component and the method to replace it, see the
“ EEPROM location diagram” section.)
• The EEPROM on the P.C. board to be replaced needs to be removed and mounted on the service P.C. board.
Replacing P.C. board and turning on power:
Procedure 2
Reading EEPROM data:
Procedure 1
• If data cannot be read, go to Method 3.
Replacing EEPROM (IC10) again (For the location of this component and the method to replace it, see the “
EEPROM location diagram” section.)
• The old EEPROM, supplied with the P.C. board to be replaced and now mounted on the service P.C. board,
needs to be replaced with the new EEPROM, supplied with the service P.C. board.
Replacing P.C. board and turning on power:
Procedure 2
Writing EEPROM data in new EEPROM:
Procedure 3
Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)
Method 3
If it is not possible to read the setting data due to the failure of the EEPROM itself -
Replacing P.C. board and turning on power:
Procedure 2
Writing EEPROM data on basis of information supplied by customer (e.g. high ceiling adjustment setting and
optional connection setting):
Procedure 3
Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...