87
Check code
Location
of
detection
Description
System
status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
AI-NET central
control
remote
controller
Check
code
Sub-code
H16
H16
SMMS
(1 series)
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
I/F
Oil detection
circuit error
All stop
The temperature
change of TK1
cannot be detected
even after
Compressor 1 starts
operating.
• Check the TK1 sensor installation.
• Check the TK1 sensor resistant
characteristics.
• Check the misconnection of TK1, TK2,
TK3, or TK4.
• Check the SV3E valve error.
• Check the oil circuit capillary clogging
and non-return valve error.
• Check the hibernating refrigerant in
compressor.
SMMS
(1 series)
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
I/F
Oil detection
circuit error
All stop
The temperature
change of TK2
cannot be detected
even after
Compressor 2 starts
operating.
• Check the TK2 sensor installation.
• Check the TK2 sensor resistant
characteristics.
• Check the misconnection of TK1, TK2,
TK3, or TK4.
• Check the SV3E valve error.
• Check the oil circuit capillary clogging
and non-return valve error.
• Check the hibernating refrigerant in
compressor.
The temperature
change of TK3
cannot be detected
even after
Compressor 3 starts
operating.
• Check the TK3 sensor installation.
• Check the TK3 sensor resistant
characteristics.
• Check the misconnection of TK1, TK2,
TK3, or TK4.
• Check the SV3E valve error.
• Check the oil circuit capillary clogging
and non-return valve error.
• Check the hibernating refrigerant in
compressor.
The temperature
change of TK4
cannot be detected
even after
Compressor 4 starts
operating, or the
temperature
difference from that
of the other TK
sensor changes only
in the specified
range for a given
time or longer.
• Check the TK4 sensor installation.
• Check the TK4 sensor resistant
characteristics.
• Check the misconnection of TK1, TK2,
TK3, or TK4.
• Check the SV3E valve error.
• Check the oil circuit capillary clogging
and non-return valve error.
• Check the hibernating refrigerant in
compressor.
SMMS-i
(4 series)
01: TK1 oil
circuit error
02: TK2 oil
circuit error
03: TK3 oil
circuit error
04: TK4 oil
circuit error
05: TK5 oil
circuit error
d7
I/F
Oil level
detection
circuit error
All stop
No temperature
change is detected
by TK1 despite
compressor 1 having
been started.
• Check for disconnection of TK1 sensor.
• Check resistance characteristics of
TK1 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK2 despite
compressor 2 having
been started.
• Check for disconnection of TK2 sensor.
• Check resistance characteristics of
TK2 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
No temperature
change is detected
by TK3 despite
compressor 3 having
been started.
• Check for disconnection of TK3 sensor.
• Check resistance characteristics of
TK3 sensor.
• Check for connection error involving
TK1, TK2, TK3, TK4, and TK5 sensors
• Check for faulty operation in SV3E or
SV3F valve.
• Check for clogging in oil equalizing
circuit capillary and faulty operation in
check valve.
• Check for refrigerant entrapment inside
compressor.
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...