28
4200FA XT 80kVA Installation and Operation Manual
5.2
Specifications – 4200FA 80kVA with Internal Transformer
Model Number
T42#3F800FAXXN
Rated Output Capacity
80 kVA
External Dimensions
(W x D x H)
41 in. x 31 in. x 74 in.
(1041 mm x 787 mm x 1880 mm)
Weight
2200 lbs (1000 kg)
Main Input
Rated Voltage
# = (B-208, N-380,Q-400/415, D-480)
Voltage Variation
4,5
+10% to -30
4,5
Rated Frequency
50/60 Hz
Number Phases / Wires
3 Phase / 3 Wire
Power Factor
1
Greater than 0.99 when in inverter mode
1
Required Input Power
76 kW when in inverter mode
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times rated current under synchronous operation
Current Limit
115% maximum
Harmonic Currents
1
Less than 4% THD
1
Optional
Bypass Input
Rated Voltage
208 / 120 Vac
Voltage Variation
+10% to –15%
Rated Frequency
50/60 Hz
Number Phases / Wires
3 Phase / 4 Wire + GND
Battery
DC Nominal (Voltage Range)
288 VDC (230 to 332 VDC)
Float Charge (Regulation)
324 VDC (
±
2%) with 2.25 V/cell
Ripple Voltage
2% R.M.S.
Rated Back-up Time
2
Refer to Battery System Manual
2
Rated Charge Current
20.0 Amps
Output
Rated Voltage
208 / 120 VAC
Rated Current
223 Amps
Rated Power Factor
0.8 lagging
Number Phases / Wires
3-phase / 4 Wire + GND
Voltage Regulation
(phase-phase)
±
2% (0-100% balanced load)
±
3% (0-100% unbalanced load)
Voltage Adjustment Range
±
5 V Manually from front key pad
Phase Displacement
±
2
°
(0-100% balanced load)
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
Operation Range
±
.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3 Hz/s
Voltage Transients
(Recovery time: 50 ms)
±
3% (100% load step change)
±
5% (loss or return of input voltage)
±
3% (transfer of bypass to inverter)
Inverter Overload Capacity
125% for 30 sec ; 150% for 5 sec
Bypass Overload Capacity
125% for 10 min.; 1000% for 10 ms
Crest Factor
2.5
Neutral Line Conductor
1.73 times line rating
Harmonic Voltage Distortion
1.5% max (linear load)
Inrush Current protection
Automatic transfer to bypass, then retransfer to inverter
Environment
Efficiency (Typical)
AC/AC – See Section 5.3; DC/AC: 83%
Heat loss to be removed
See Section 5.3
Audible Noise
75 dB (A) at 3.3 ft. (1 m) from the units front display
Operating Temperature
0 – 104
°
F (0 – 40
°
C); optimal operating temperature: 77
°
F (25
°
C)
Operating Humidity
Less than 90% RH (non-condensing)
Altitude
3
Less than 6600 ft. (2000 m)
3
1 - Specified at rated conditions under balanced linear loads.
2 - Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. An initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
3 - At 6600 ft. (2000 m) above sea level, output capacity should be derated by 3% (Consult factory for higher elevations).
4 – Continuous operation at -10% to -15% Vin requires EITHER derating the output capacity 15% OR decreasing the maximum Operating Temperature
to 90
°
F ( 32
°
C).
5 – Continuous operation at -15% to -30% Vin requires derating the output capacity 30%.