18
model 3000 Ethernet Module / DS Connection Module Operation Manual
Chapter 3 Setting
3
Each of the switches for EN751 and EN761 is described inTable 3-5.
Operation Mode
• Normal:
The EN7 module is operated in standard condition.
• Download:
Used for downloading firmware to the EN7 module program ROM
(flash PROM). This mode is set in upgrading the firmware version.
• Test Program: Used for operating the test program. Never use this mode.
IP Address Type
• Class B (General):
Used for connecting an Ethernet of integrated controllers or a
general Ethernet.
• TOSDIC-CIE 1200:
Used for connecting a TOSDIC-CIE 1200 Ethernet. (The system
operates according to the data set in the flash PROM.)
• Setting from Tool:
Used for operating the EN6 modules with the network
parameters set from the Engineering tool.
Table 3-5 Operation Mode Setting Table (FN711)
Switch No.
Name
Function
Setting
Default
(Before
shipment)
1
M0
Operation mode
M1
M0
Operation
M1=off
M0=off
(Normal setting)
off
off
Normal
off
on
Reserve
2
M1
on
off
Reserve
on
on
Memory clear
3
TEST
Test program
on : Test mode,
off : Normal mode
off
4
TAGL
FROM tag load
on : Tag load from FROM,
off : Non-operation
off
5
DL
Download
on : Download mode,
off : Normal mode
off
6
SEL
Serial switching
on : TOOL=Tool Internal=Debug,
off : TOOL debug Internal=Tool
off
7
DLSP
DL speed
on : 115200BPS,
off : 57600BPS
off
8
DBB
Debug break
Normally off
off
Summary of Contents for 3000 series
Page 13: ...CONTENTS 6F8C0878 xi E Sample Programs 91 F Return Code List 103 G Option switch List 107 ...
Page 14: ......
Page 26: ......
Page 72: ......
Page 76: ......
Page 82: ......
Page 100: ......
Page 102: ......
Page 104: ......
Page 116: ......
Page 120: ......
Page 122: ......
Page 126: ......