TE Series
Digital Solid State Soft Starters 18 – 1250A
88
Appendix 6 (cont.) Soft Starter Settings Record
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
Setting
F024
Pump Flex Dec
e
l
Mode
Pump Flex Control /
Deceleration Ramp
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
1
0
Disabled
F025
Begin Decel Level (BDL),
Immediate Drop Down Torque
0 - 100 % of Output Voltage
1%
60%
F026
Decel Shut Off Voltage
0 to (BDL minus 1)% Voltage
1%
30%
F027
Decel Ramp Time
1 – 60 Seconds
1 second
10
seconds
F028
Restart
Restart Delay Time
(Sequential Start Delay)
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
1 second
0
Disabled
F029
Reserved for Factory Use
F030
Run Timer
a
nd Time Clock Co
n
troller
Mo
des
Process Control Timer
Selection
0 = Disabled (No timer operation)
1 = Minimum Batch Run Timer
2 = Permissive Run Timer
1
0
Disabled
F031
Run Timer Time
for use in F030 above
1-9999 minutes after a Start
Command or Start Event from TCC
1 1
F032
24hr
Time Clock Controller (TCC)
Start Event Mode.
Chose from “One Shot”
or 1 to 7 “Start Events”
in F033 – F039
Run time for this mode comes
from F030 above.
Start Event Cycle (SEC) Settings
0 = One Shot: Start Event comes
from Start command only
1 = Loop SEC every day
2 = Loop SEC every 2
nd
day
3 = Loop SEC every 3
rd
day
4 = Loop SEC. every 4
th
day
5 = Loop SEC. every 5
th
day
6 = Loop SEC. every 6
th
day
7 = Loop SEC one day per week
8 = Single 24hr SEC
(until programmed again)
1
0
One Shot
F033
Start Event #1 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F034
Start Event #2 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F035
Start Event #3 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F036
Start Event #4 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F037
Start Event #5 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F038
Start Event #6 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F039
Start Event #7 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF