TE Series
Digital Solid State Soft Starters 18 – 1250A
32
5.5.7 Process Timer Features
5.5.8
Current and Ground Fault Protection Features
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F030
Run Timer
a
nd Time Clock Co
n
troller
Mo
des
Run Timer Selection
0 = Disabled (No timer operation)
1 = Minimum (Batch) Run Timer
2 = Permissive Run Timer
1
0
Disabled
5.6.7
and
Append.
4
F031
Run Timer Time
for use in F030 above
1-9999 minutes after a Start
Command or Start Event from TCC
1 1
F032
24hr
Time Clock Controller (TCC)
Start Event Mode.
Chose “One Shot”
or 1 to 7 “Start Events”
from F033 – F039
Run time for this mode comes
from F030 above.
Start Event Cycle (SEC) Settings.
1 = Loop SEC every day
2 = Loop SEC every 2
nd
day
3 = Loop SEC every 3
rd
day
4 = Loop SEC every 4
th
day
5 = Loop SEC every 5
th
day
6 = Loop SEC every 6
th
day
7 = Loop SEC one day per week
8 = Single 24hr SEC
(until programmed again)
0 = One Shot: Start Event comes
from Start command only
1
0
One Shot
F033
Start Event #1 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F034
Start Event #2 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F035
Start Event #3 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F036
Start Event #4 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F037
Start Event #5 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F038
Start Event #6 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
F039
Start Event #7 Start Time
00:00-23:59 (hh:mm) or OFF
1
OFF
Table 5.5.7: Run Timer and Time Clock Controller Function Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F040
Current
an
d Gr
oun
d Fa
ult Pr
ot
ectio
n
Current Imbalance Trip
0 = Disabled, or
5 - 30% imbalance
1%
0
Disabled
5.6.8
F041
Current Imbalance Trip Delay
1 - 20 seconds
1 second
2
seconds
F042
Over Current Trip
0 = Disabled, or
100 - 300% of motor FLA
1%
0
Disabled
F043
Over Current Trip Delay
1 - 20 seconds
1 second
1 second
F044
Under Current Trip
0 = Disabled, or
10 - 90% of motor FLA
1%
0
Disabled
F045
Under Current Trip Delay
1 - 60 seconds
1 second
2
seconds
F046 Ground
Fault
Trip
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1%
0
Disabled
F047
Ground Fault Trip Delay
1 - 60 seconds
1 second
2
seconds
Table 5.5.8: Current and Ground Protection Features Group