B-10
1600XPi Series UPS Installation and Operation Manual – 60616-014
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
270
Output Current before Tranformer Compensation
Iout B4 Comp.
-
-
-
R/W
R/W
0
Units: 0.1
A
271
Inverter Mode
A Compensation
Comp.
Ainv
-
-
-
R/W
R/W
2
Range: 0 – 512
Units: /128
272
Inverter Mode B Compensation
Comp. Binv
-
-
-
R/W
R/W
10
Range: 0 – 512
Units: /128
273
Inverter Mode C Compensation
Comp. Cinv
-
-
-
R/W
R/W
0
Range: 0 – 512
Units: /128
274
Bypass Mode
A Compensation
Comp.
Abyp
-
-
-
R/W
R/W
3
Range: 0 – 512
Units: /128
275
Bypass Mode B
Compensation
Comp. Bbyp
-
-
-
R/W
R/W
7
Range: 0 – 512
Units: /128
276
Bypass Mode C Compensation
Comp. Cbyp
-
-
-
R/W
R/W
1
Range: 0 – 512
Units: /128
277
Overload T
ime
Window
OL
T
ime
Wndw
-
-
-
R/W
R/W
10
Range: 0 – 30
Units: min
278
Rated Output Primary
Transformer
Rated
OutXfmer(P)
-
-
-
R/W
R/W
230
Range: 200 – 300
Units: V
279
50 Hz Derating
50Hz Derating
-
-
-
R/W
R/W
100
Range: 50 – 150
Units: %
280
60 Hz Derating
60Hz Derating
-
-
-
R/W
R/W
100
Range: 50 – 150
Units: %
301
Bypass Power Supply Configuration
Bypass Config
R
R
R
R
R
Always, the same as input configuration
0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording features
302
Number of Bypass phases
No Of Bypass Line
R
R
R
R/W
R/W
1
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...