D5
1600XPi Series UPS Installation and Operation Manual – 60616-014
14kVA – H3BG2L140C61T
(Runtimes are approximate)
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output Volt
-
age
Rated I
Rated Load
%
Output
Watts
# Batt
# Strings
Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
2
288
112
14
0.85
240
58.33
0.20
2380
24
2
288
60
14
0.85
240
58.33
0.30
3570
24
2
288
43
14
0.85
240
58.33
0.40
4760
24
2
288
29
14
0.85
240
58.33
0.50
5950
24
2
288
21
14
0.85
240
58.33
0.60
7140
24
2
288
16
14
0.85
240
58.33
0.70
8330
24
2
288
13
14
0.85
240
58.33
0.80
9520
24
2
288
11
14
0.85
240
58.33
0.90
10710
24
2
288
10
14
0.85
240
58.33
1.00
11900
24
2
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output Volt
-
age
Rated I
Rated Load
%
Output
Watts
# Batt
# Strings
Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
5
288
300
14
0.85
240
58.33
0.20
2380
24
5
288
150
14
0.85
240
58.33
0.30
3570
24
5
288
98
14
0.85
240
58.33
0.40
4760
24
5
288
78
14
0.85
240
58.33
0.50
5950
24
5
288
63
14
0.85
240
58.33
0.60
7140
24
5
288
53
14
0.85
240
58.33
0.70
8330
24
5
288
45
14
0.85
240
58.33
0.80
9520
24
5
288
40
14
0.85
240
58.33
0.90
10710
24
5
288
35
14
0.85
240
58.33
1.00
11900
24
5
288
30
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output Volt
-
age
Rated I
Rated Load
%
Output
Watts
# Batt
# Strings
Nominal
Runtime
14
0.85
240
58.33
0.10
1190
24
8
288
300
14
0.85
240
58.33
0.20
2380
24
8
288
240
14
0.85
240
58.33
0.30
3570
24
8
288
150
14
0.85
240
58.33
0.40
4760
24
8
288
120
14
0.85
240
58.33
0.50
5950
24
8
288
98
14
0.85
240
58.33
0.60
7140
24
8
288
82
14
0.85
240
58.33
0.70
8330
24
8
288
72
14
0.85
240
58.33
0.80
9520
24
8
288
63
14
0.85
240
58.33
0.90
10710
24
8
288
55
14
0.85
240
58.33
1.00
11900
24
8
288
51
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......