UPS Protection System
40
I
nput
Abnormal
Overheating
*Static
switch
Bypass
Overvoltage/
Undervoltage
Power flow
Current Limit
Overload
Input
_
+
Batteries
Low Battery
Level
Overcurrent
MCCB
Output
Rectifier/
charger/
chopper
Inverter
Line
filter
Surge
absorber
* Switches are
solid state devices
System Protection Functions
The following charts show the built-in UPS system fault protection functions on the
2.4 kVA, 3.6 kVA, 6.0 kVA and 8.0 kVA models.
Protection Item
LCD Message
Cause
Output overload
Output overvoltage
Control malfunction;
chip error
Output undervoltage
Control malfunction;
wire disconnected
Inverter OL: Transfer to bypass;
inverter stopped
Bypass OL: inverter, chopper,
and bypass stopped
Overload; short circuit
at load
Bypass operation;
chopper and inverter are stopped
Operation Mode
After Fault
Yes; continuous buzzer
See 'Audible Alarm Functions'
on page 24
Audible Alarm
Bypass OL: Fault lamp "on"
RED fault LED "on"
Visible Alarm
Fault relay open;
Inverter OL: No fault lamp
Bypass OL: Bypass relay open
Inverter OL: Bypass relay closed
Relay Contact
Alarm
Fault relay closed;
bypass relay closed
No
Bypass OL: No
Inverter OL: Yes if bypass is OK
Auto-retransfer
Built-In UPS Fault Protection Functions
TOSHIBA
System Protection Features
The following schematic shows the electrical locations of the protection devices on the
2.4 kVA, 3.6 kVA, 6.0 kVA and 8.0 kVA UPS models.
OUT-OV
OUT-UV
OVER LOAD
Isolation
Transformer
(optional)
Input
fuses
Output
fuses