TOSHIBA
SAVE THESE INSTRUCTIONS-
This manual contains important instructions
for models UC0A1A005C6T, UC0A1A006C6, UC0A1A007C6T, UC0AIA008C6, UC0A1A010C6,
UC0A1A010C6T, UC0A1A012C6, UC0A1A015C6, UC0A1A015C6T, and UC0A1A020C6 that should
be followed during the installation and maintenance of the UPS and it's batteries.
- The maximum ambient temperature in which this UPS unit should be operated or stored is
104 deg F (40 deg C).
- The nominal battery voltage range is indicated in Section 5.6 on page 5-7.
- Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
- When replacing batteries, use the same number and type of one of the following sealed, lead-acid
batteries:
Model Capacity
Manufacturer
Type
Quantity
500 VA
Panasonic
LCR 12V6.5BP
3
Panasonic
LCR 12V7.2P
3
Yuasa
NP7 - 12
3
600 VA
Panasonic
LCR 12V6.5BP
3
Panasonic
LCR 12V7.2P
3
Yuasa
NP7 - 12
3
750 VA
Panasonic
LCR 12V6.5BP
4
Panasonic
LCR 12V7.2P
4
Yuasa
NP7 - 12
4
800 VA
Panasonic
LCR 12V6.5BP
4
Panasonic
LCR 12V7.2P
4
Yuasa
NP7 - 12
4
1000 VA
Panasonic
LCR 12V6.5BP
5
Panasonic
LCR 12V7.2P
5
Yuasa
NP7 - 12
5
1200 VA
Panasonic
LCR 12V6.5BP
6
Panasonic
LCR 12V7.2P
6
Yuasa
NP7 - 12
6
1500 VA
Panasonic
LCR 12V6.5BP
6
Panasonic
LCR 12V7.2P
6
Yuasa
NP7 - 12
6
2000 VA
Panasonic
LCR 12V6.5BP
8
Panasonic
LCR 12V7.2P
8
Yuasa
NP7 - 12
8
-
CAUTION-
Do not dispose of the batteries in a fire. The batteries may explode.
-
CAUTION-
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes
and skin and could also be toxic.
-
CAUTION-
A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on the batteries:
1) Verify that the UPS is off and that the power cord is disconnected from the power
source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not lay tools or metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground.
Contact with any part of a grounded battery can result in electrical
shock.
The likelihood of such shock will be reduced if such grounds are removed during
installation and maintenance.