Instruction manual - SAS 16.6 - 1. Installation conditions
300801_en - 12/12
1-11
1.5.2.
Installation characteristics
Main power connection
The connection system for the machine to the mains is provided by the cable to the bottom of
the electric cabinet (see
).
The machine SAS 16.6 is protected from short circuits and power surges by an FR2 circuit breaker of
the electromagnetic and thermal type.
Connect the power according to the real network measurements. The tolerances indicated in the
table must not be surpassed in any event.
Specifications
Name
Unit
Value
Power active
kW
9
Installed power
kVA
15
Specifications
Network power foreseen (V)
Previously
delayed fuse (A)
Frequency
foreseen (Hz)
Entrance
section
(mm
2
)
200 – 20 Nm
40
50 / 60
– 10
230 +/– 5%
– 40
50 / 60
– 10
380 +/– 5%
– 32
50 / 60
– 4
400 +/– 5%
– 32
50 / 60
– 4
420 +/– 5%
– 32
50 / 60
– 4
440 +/– 5%
– 20
50 / 60
– 4
460 +/– 5%
– 20
50 / 60
– 2.5
480 +/– 5%
– 20
50 / 60
– 2.5
500 +/– 5%
– 20
50 / 60
– 2.5
Summary of Contents for SAS 16.6
Page 2: ......
Page 6: ...300801_en 12 12 Instruction manual SAS 16 6 ...
Page 22: ...300801_en 12 12 1 Installation conditions Instruction manual SAS 16 6 1 14 Fig 8 ...
Page 24: ...300801_en 12 12 1 Installation conditions Instruction manual SAS 16 6 1 16 Fig 9 ...
Page 27: ...Instruction manual SAS 16 6 2 Installation 300801_en 12 12 2 1 2 Installation ...
Page 33: ...Instruction manual SAS 16 6 2 Installation 300801_en 12 12 2 7 Fig 3 ...
Page 46: ...300801_en 12 12 2 Installation Instruction manual SAS 16 6 2 20 ...